If you equip the drive with a main contactor or breaker, make sure that it restores
the drive input power after a short break. The contactor must either re-connect
after the break automatically, or remain closed over the break. Depending on the
contactor control circuit design, this can require an additional hold circuit,
uninterruptible auxiliary power supply or auxiliary power supply buffering.
Note: If the power loss lasts so long that the drive trips on undervoltage, a fault
reset and a fresh start command is required to continue operation.
Implement the power-loss ride-through function as follows:
1.
Enable the power-loss ride-through function of the drive (parameter 30.31).
2.
If the installation is equipped with a main contactor, prevent its tripping at
the input power break. For example, use a time delay relay (hold) in the
contactor control circuit.
3.
Enable the automatic restart of the motor after a short power supply break:
•
Set the start mode to automatic (parameter 21.01 or 21.19, depending on
the motor control mode being used).
•
Define the automatic restart time (parameter 21.18).
WARNING!
Make sure that a flying restart of the motor will not cause any danger. If you
are in doubt, do not implement the power loss ride-through function.
Using power factor compensation capacitors with the drive
Power factor compensation is not needed with AC drives. However, if a drive is to
be connected in a system with compensation capacitors installed, note the
following restrictions.
WARNING!
Do not connect power factor compensation capacitors or harmonic filters
to the motor cables (between the drive and the motor). They are not meant
to be used with AC drives and can cause permanent damage to the drive or
themselves.
If there are power factor compensation capacitors in parallel with the input of the
drive:
1.
Do not connect a high-power capacitor to the power line while the drive is
connected. The connection will cause voltage transients that may trip or even
damage the drive.
2.
If capacitor load is increased/decreased step by step when the AC drive is
connected to the power line, make sure that the connection steps are low
enough not to cause voltage transients that would trip the drive.
Guidelines for planning the electrical installation 83
Содержание ACH580-31
Страница 1: ... ABB INDUSTRIAL DRIVES ACH580 31 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 30: ...30 ...
Страница 39: ...Operation principle 39 ...
Страница 56: ...56 ...
Страница 90: ...90 ...
Страница 112: ...R3 1 7 N m 112 Electrical installation IEC ...
Страница 113: ...R6 1 7 N m Electrical installation IEC 113 ...
Страница 114: ...R8 1 7 N m 114 Electrical installation IEC ...
Страница 130: ...R3 Max 250 mA 130 Electrical installation North America NEC ...
Страница 131: ...R6 Electrical installation North America NEC 131 ...
Страница 150: ...150 ...
Страница 152: ...152 ...
Страница 166: ... Fan arrow must point up 166 Maintenance ...
Страница 189: ... Package dimensions and weights R6 R3 R8 26 61 11 38 16 65 23 54 25 74 39 06 15 75 45 59 19 76 Technical data 189 ...
Страница 212: ...212 ...
Страница 214: ...R3 IP21 UL Type 1 3AXD50000028643 214 Dimension drawings ...
Страница 215: ...R3 Option B056 IP55 UL Type 12 3AXD50000045321 Dimension drawings 215 ...
Страница 216: ...R6 IP21 UL Type 1 3AXD50000037446 216 Dimension drawings ...
Страница 217: ...R6 Option B056 IP55 UL Type 12 3AXD50000045351 Dimension drawings 217 ...
Страница 218: ...R8 IP21 UL Type 1 3AXD50000147052 218 Dimension drawings ...
Страница 219: ...R8 Option B056 IP55 UL Type 12 3AXD50000147052 Dimension drawings 219 ...
Страница 220: ...220 ...
Страница 242: ...242 ...
Страница 250: ...250 ...
Страница 254: ...254 ...
Страница 261: ...Dimension drawings The dimensions are in millimeters CAIO 01 bipolar analog I O adapter module 261 ...
Страница 262: ...262 ...
Страница 268: ...268 ...
Страница 275: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 275 ...
Страница 276: ...276 ...
Страница 282: ...282 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...