Requirement for
Nominal AC supply
voltage
ABB du/dt and common mode filters, insulated N-
end motor bearings
Motor insulation system
100 kW < P
N
< 350 kW or
IEC 315 < frame size <
IEC 400
P
N
< 100 kW or frame
size < IEC 315
134 hp < P
N
< 469 hp or
NEMA 500 < frame size <
NEMA 580
P
N
< 134 hp or frame size
< NEMA 500
+ N or CMF
+ N or CMF
Standard:
Û
LL
= 1300 V
U
N
≤ 420 V
+ N + d
u
/d
t
+ CMF
+ d
u
/d
t
+ (N or CMF)
Standard:
Û
LL
= 1300 V
420 V <
U
N
< 500 V
or
+ N or CMF
+ N or CMF
Reinforced:
Û
LL
= 1600 V,
0.2 microsecond rise time
+ N + d
u
/d
t
+ CMF
+ d
u
/d
t
+ (N or CMF)
Reinforced:
Û
LL
= 1600 V
500 V <
U
N
≤ 600 V
or
+ N + CMF
+ N or CMF
Reinforced:
Û
LL
= 1800 V
+ N + d
u
/d
t
+ CMF
+ N + d
u
/d
t
Reinforced:
Û
LL
= 1800 V
600 V <
U
N
≤ 690 V
+ N + CMF
+ N + CMF
Reinforced:
Û
LL
= 2000 V,
0.3 microsecond rise
time
1)
1) If the intermediate DC circuit voltage of the drive is increased from the nominal level due to long term resistor braking
cycles, check with the motor manufacturer if additional output filters are needed in the applied drive operation range.
Additional data for calculating the rise time and the peak line-to-line voltage
The diagrams below show the relative peak line-to-line voltage and rate of change of voltage
as a function of the motor cable length. If you need to calculate the actual peak voltage and
voltage rise time considering the actual cable length, proceed as follows:
•
Peak line-to line voltage: Read the relative
Û
LL
/
U
N
value from the diagram below and
multiply it by the nominal supply voltage (
U
N
).
•
Voltage rise time: Read the relative values
Û
LL
/
U
N
and (d
u
/d
t
)/
U
N
from the diagram
below. Multiply the values by the nominal supply voltage (
U
N
) and substitute into equation
t = 0.8 ·
Û
LL
/(d
u
/d
t
).
70 Guidelines for planning the electrical installation
Содержание ACH580-04
Страница 1: ... ABB DRIVES FOR HVAC ACH580 04 drive modules Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 54: ...54 ...
Страница 88: ...88 ...
Страница 100: ...100 ...
Страница 118: ...118 ...
Страница 122: ...122 ...
Страница 124: ...124 ...
Страница 128: ...3 6 5 5 128 Maintenance ...
Страница 134: ...134 ...
Страница 156: ...R10 standard configuration 156 Dimension drawings ...
Страница 157: ...R10 with E208 0H354 H356 H370 0H371 Dimension drawings 157 ...
Страница 158: ...R10 with option B051 158 Dimension drawings ...
Страница 159: ...R10 with option E208 H356 P906 192 Tools R10 3 1 Dimension drawings 159 ...
Страница 160: ...R10 with option E208 0H371 H356 0H354 H370 P906 Tools 191 R10 2 1 160 Dimension drawings ...
Страница 161: ...R10 with option B051 P906 190 Tools R10 1 1 Dimension drawings 161 ...
Страница 162: ...R11 standard configuration 162 Dimension drawings ...
Страница 163: ...R11 with option E208 0H371 H356 0H354 H370 Dimension drawings 163 ...
Страница 164: ...R11 with option B051 164 Dimension drawings ...
Страница 165: ...R11 with option E208 H356 P906 Dimension drawings 165 ...
Страница 166: ...R11 with option E208 0H371 H356 0H354 H370 P906 166 Dimension drawings ...
Страница 167: ...R11 with option B051 P906 Dimension drawings 167 ...
Страница 186: ... Declaration of conformity 186 The Safe torque off function ...
Страница 206: ...Dimension drawing 206 External control unit option P906 ...
Страница 211: ...Dimension drawing The dimensions are in millimeters and inches CHDI 01 115 230 V digital input extension module 211 ...
Страница 212: ...212 ...
Страница 224: ...224 ...
Страница 226: ...226 ...
Страница 234: ...234 ...