ACH550-UH User’s Manual
Embedded fieldbus
Actual values
The contents of the register addresses 40005…40012 are
ACTUAL
VALUES
and are:
•
Specified using parameters 5310…5317.
•
Read-only values containing information on the operation of the drive.
•
16-bit words containing a sign bit and a 15-bit integer.
•
When negative values, written as the two’s complement of the corresponding
positive value.
•
Scaled as described earlier in
.
Exception codes
Exception codes are serial communication responses from the drive.
The ACH550
supports the standard Modbus exception codes defined below.
Exception
Code
Name
Meaning
01
ILLEGAL
FUNCTION
Unsupported Command
02
ILLEGAL
DATA
ADDRESS
The data address received in the query is not allowable. It is not
a defined parameter/group.
03
ILLEGAL
DATA
VALUE
A value contained in the query data field is not an allowable
value for the ACH550, because it is one of the following:
• Outside min. or max. limits.
• Parameter is read-only.
• Message is too long.
• Parameter write not allowed when start is active.
• Parameter write not allowed when factory macro is selected.
Содержание ACH550-UH HVAC
Страница 2: ......
Страница 8: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 32: ...1 32 ACH550 UH User s Manual Installation ...
Страница 66: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 186: ...1 186 ACH550 UH User s Manual Parameters ...
Страница 190: ...1 190 ACH550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...ACH550 UH User s Manual 1 333 Technical data ...