ACH550-UH User’s Manual
1-173
Parameters
8112
LOW FREQ 1
0.0…500.0 Hz
0.1 Hz
30.0 Hz (US)
Sets the frequency limit used to stop the first auxiliary motor. The first auxiliary motor stops if:
• Only one (the first) auxiliary motor is running.
• ACH550 output frequency drops below the limit:
8112 - 1.
• Output frequency stays below the relaxed limit
(8112 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
After the first auxiliary motor stops:
• Output frequency increases by the value =
(8109
START
FREQ
1) - (8112
LOW
FREQ
1).
• In effect, the output of the speed regulated motor increases to
compensate for the loss of the auxiliary motor.
See the figure, where:
• A = (8109
START
FREQ
1) - (8112
LOW
FREQ
1)
• B = Output frequency decrease during the stop delay.
• C = Diagram showing auxiliary motor’s run status as
frequency decreases (1 = On).
• Grey path = Shows hysteresis – if time is reversed, the path
backwards is not the same. For details on the path for
starting, see the diagram at 8109
START
FREQ
1.
Note:
8112
LOW
FREQ
1 value must be between:
• (2007
MINIMUM
FREQ
) +1.
• 8109
START
FREQ
1
8113
LOW FREQ 2
0.0…500.0 Hz
0.1 Hz
30.0 Hz (US)
Sets the frequency limit used to stop the second auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The second auxiliary motor stops if:
• Two auxiliary motors are running.
• ACH550 output frequency drops below the limit: 8113 - 1.
• Output frequency stays below the relaxed limit (8113 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
8114
LOW FREQ 3
0.0…500.0 Hz
0.1 Hz
30.0 Hz (US)
Sets the frequency limit used to stop the third auxiliary motor.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
The third auxiliary motor stops if:
• Three auxiliary motors are running.
• ACH550 output frequency drops below the limit: 8114 - 1.
• Output frequency stays below the relaxed limit (8114 + 1 Hz) for at least the time: 8116
AUX
MOT
STOP
D
.
8115
AUX MOT START D
0.0…3600.0 s
0.1 s
5.0 s
Sets the Start Delay for the auxiliary motors.
• The output frequency must remain above the start frequency limit (parameter 8109, 8110, or 8111) for this time
period before the auxiliary motor starts.
• See 8109
START
FREQ
1 for a complete description of the operation.
8116
AUX MOT STOP D
0.0…3600.0 s
0.1 s
3.0 s
Sets the Stop Delay for the auxiliary motors.
• The output frequency must remain below the low frequency limit (parameter 8112, 8113, or 8114) for this time
period before the auxiliary motor stops.
• See 8112
LOW
FREQ
1 for a complete description of the operation.
Group 81: PFA Control
Code Description Range
Resolution
Default
S
t
t
f
(Hz)
f
MIN
f
MAX
P 8116
(P 8112)-1
B
1
0
C
P 8112
P 8109
A
A
Содержание ACH550-BCR
Страница 4: ...iv Manual contents ...
Страница 5: ...ACH550 UH User s Manual 1 1 ACH550 UH HVAC Drives 1 550 HP User s Manual 2016 ABB All Rights Reserved ...
Страница 6: ......
Страница 12: ...1 8 ACH550 UH User s Manual Table of contents ...
Страница 36: ...1 32 ACH550 UH User s Manual Installation ...
Страница 70: ...1 66 ACH550 UH User s Manual Application macros ...
Страница 335: ...ACH550 UH User s Manual 1 331 Technical data ...
Страница 348: ......
Страница 382: ...2 36 ACH550 E Clipse Bypass User s Manual Start up ...
Страница 398: ...2 52 ACH550 E Clipse Bypass User s Manual Bypass functions overview ...
Страница 406: ...2 60 ACH550 E Clipse Bypass User s Manual Application macros ...
Страница 544: ...2 198 ACH550 E Clipse Bypass User s Manual Embedded fieldbus ...
Страница 584: ...2 238 ACH550 E Clipse Bypass User s Manual Diagnostics ...
Страница 608: ......
Страница 612: ...3 6 ACH550 UH User s Manual Table of contents ...
Страница 622: ...3 16 ACH550 PCR PDR User s Manual Installation ...
Страница 641: ......