1. If there is double or reinforced insulation between the sensor and the live parts of
the motor: You can connect the sensor directly to the analog/digital input(s) of the
drive. See the control cable connection instructions.
2. If there is basic insulation between the sensor and the live parts of the motor: You
can connect the sensor to the analog/digital input(s) of the drive. All other circuits
connected to the digital and analog inputs (typically extra-low voltage circuits) must
be:
•
protected against contact, and
•
insulated with basic insulation from other low-voltage circuits. The insulation
must be rated for the same voltage level as the drive main circuit.
Note:
Extra-low voltage circuits (for example, 24 V DC) typically do not meet these
requirements.
As an alternative, you can connect the sensor with basic insulation to the
analog/digital input(s) of the drive, if you do not connect any other external control
circuits to the drive digital and analog inputs.
3. You can connect a sensor to a digital input of the drive via an external relay. The
sensor and the relay must form a double or reinforced insulation between the motor
live parts and the digital input of the drive.
Protecting the drive against ground faults
The drive is equipped with an internal ground fault protective function to protect the unit
against ground faults in the motor and motor cable. This function is not a personnel
safety or a fire protection feature. See the firmware manual for more information.
■
Residual current device compatibility
The drive is suitable to be used with residual current devices of Type B.
Note:
As standard, the drive contains capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause nuisance faults in residual current devices.
Implementing the Emergency stop function
For safety reasons, install the emergency stop devices at each operator control station
and at other operating stations where emergency stop may be needed. Design the
emergency stop according to the applicable standards.
You can use the Safe torque off function of the drive to implement the Emergency stop
function.
Note:
Pressing the stop (off) key on the control panel of the drive does not generate an
emergency stop of the motor or separate the drive from dangerous potential.
Guidelines for planning the electrical installation 57
Содержание ACH480
Страница 1: ... ABB DRIVES FOR HVAC ACH480 drives Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 14: ...14 ...
Страница 22: ...22 ...
Страница 28: ...28 ...
Страница 38: ...38 ...
Страница 44: ...44 ...
Страница 60: ...60 ...
Страница 86: ...86 ...
Страница 110: ...110 ...
Страница 114: ...114 ...
Страница 122: ...122 ...
Страница 156: ...Frame R1 Frame R1 front side IP20 UL open type 156 Dimension drawings ...
Страница 157: ... Frame R1 bottom rear IP20 UL open type Dimension drawings 157 ...
Страница 158: ... Frame R1 front side UL Type 1 kit installed 158 Dimension drawings ...
Страница 159: ... Frame R1 bottom rear UL Type 1 kit installed Dimension drawings 159 ...
Страница 160: ...Frame R2 Frame R2 front side IP20 UL open type 160 Dimension drawings ...
Страница 161: ... Frame R2 bottom rear IP20 UL open type Dimension drawings 161 ...
Страница 162: ... Frame R2 front side UL Type 1 kit installed 162 Dimension drawings ...
Страница 163: ... Frame R2 bottom rear UL Type 1 kit installed Dimension drawings 163 ...
Страница 164: ...Frame R3 Frame R3 front side IP20 UL open type 164 Dimension drawings ...
Страница 165: ... Frame R3 bottom rear IP20 UL open type Dimension drawings 165 ...
Страница 166: ... Frame R3 front side UL Type 1 kit installed 166 Dimension drawings ...
Страница 167: ... Frame R3 bottom rear UL Type 1 kit installed Dimension drawings 167 ...
Страница 168: ...Frame R4 Frame R4 front side IP20 UL open type 168 Dimension drawings ...
Страница 169: ... Frame R4 bottom rear IP20 UL open type Dimension drawings 169 ...
Страница 170: ... Frame R4 front side UL Type 1 kit installed 170 Dimension drawings ...
Страница 171: ... Frame R4 bottom rear UL Type 1 kit installed Dimension drawings 171 ...
Страница 172: ...172 ...
Страница 180: ...180 ...
Страница 198: ... Declaration of conformity 198 The Safe torque off function ...
Страница 206: ...Dimensions 206 BIO 01 I O extension module ...
Страница 212: ...Dimensions 3AXD50000031148 rev A 212 BREL 01 relay output extension module ...