Environmental limits
Transportation
Storage
Operation
-
-
4000 m (13123 ft.)
Installation site altitude
-40 °C to +70 °C
-40 °C to +70 °C
-20 °C to +55 °C
Air temperature
(-40 °F to 158 °F)
(-40 °F to 158 °F)
(-4 °F to 131 °F)
95% (non-condensing)
Relative humidity
-
-25 °C to +70 °C
-20 °C to +70 °C
Temperature inside the panel
(-13 °F to 158 °F)
(-4 °F to 158 °F)
Note:
Accuracy of real time clock is not good at very high and very low temperatures.
IEC compliance
Transportation
Operation
3C3
Contamination levels
(IEC 60721-3-3, IEC 60721-3-2,
IEC 60721-1-3-1)
class 2M3 in acc. with
61800-5-1 ed 2.
Sinusoidal vibration
EN 60082-2-6
EN 60082-2-6 test Fc (1g)
class 2M2 in acc. with
class 3M4 in acc. with
Shock
EN 60082-2-27
EN 60062-2-27
-
IEC-60068-2-32, drop height
Free fall
1 m. (3.3 ft.)
-
IEC 61000-4-2, IEC 61000-4-3,
EMC compliance
IEC 61000-4-4, IEC 61000-4-6
(EN 61800-3: 2004 +A1: 2012)
LCD specifications
FSTN, negative transmissive
LCD type
-20 °C to +70 °C (-4 °F to 158 °F)
Operating temperature
-40 °C to +80 °C (-40 °F to 176 °F)
Storage temperature
-40 °C to +80 °C (-40 °F to 176 °F)
Transportation temperature
IC UC1698U
Driver
Compliant
ROHS
± 0.2
General tolerance
Note:
Response time of LCD display is slow at/below 0 °C (32 °F).
Bluetooth interface
Bluetooth 4.0 Dual mode (smart ready),
Bluetooth standard
Bluetooth classic,
Bluetooth LE (low energy)
Bluetooth
®
Qualified Design
Certification
Internal inverted-F on PCB
Antenna type
Technical data 77
Содержание ACH-AP-H
Страница 1: ... OPTIONS FOR ABB DRIVES ACS AP I S W and ACH AP H W Assistant control panels User s manual ...
Страница 2: ......
Страница 4: ......
Страница 12: ...12 ...
Страница 16: ...Once you are in the Home view the control panel is ready for use 16 Installation and start up ...
Страница 26: ...26 ...
Страница 32: ...32 ...
Страница 52: ...52 ...
Страница 58: ...58 ...
Страница 66: ...66 ...
Страница 70: ...70 ...
Страница 74: ...74 ...