Range
0...10 V
-10...+10
V
0...20 mA 4...20 mA Digital
input
Digital value
Decimal
Hex.
Measured
value too
low
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Underflow <0.0000
<-11.7589 <0.0000
<0.0000
-32768
8000
The represented resolution corresponds to 16 bits.
Input ranges resistance temperature detector
Range
Pt100 /
Pt1000
-50...70 °C
Pt100 / Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal
Hex.
Overflow
> 80.0 °C
> 450.0 °C
> 160.0 °C
32767
7FFF
Measured
value too
high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Normal range 70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C
0.0 °C
0.0 °C
0
0000
Normal range -0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50,0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow
< -60.0 °C
< -60.0 °C
< -60.0 °C
-32768
8000
Device specifications
Communication interface modules (S500) > Modbus
2022/01/31
3ADR010278, 3, en_US
762