Parameterization
Firmware version
Configuration
Firmware version > V2.0.0
The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name
Value
Internal value Internal
value, type
Default
EDS Slot /
Index
Module ID
1
)
Internal
1810
WORD
1810
0x0Y01
Ignore module
see table
2
)
Internal
Yes
No
BYTE
No
not for FBP
Parameter
length
Internal
8
BYTE
8
0xY02
Check supply off
0
BYTE
1
0xY03
on
1
Fast counter
3
)
0
:
10
4
)
0
:
10
BYTE
0
not for FBP
Behavior out-
puts at comm.
error
5
)
Off Last value
Last value 5
sec Last value
10 sec Substi-
tute value
Substitute
value 5 sec
Substitute
value 10 sec
0
1
6
11
2
7
12
BYTE
Off
0x00
0x0Y07
2
)
Setting
Description
On
Error LED lights up at errors of all error classes, Failsafe
mode off
Off by E4
Error LED lights up at errors of error classes E1, E2 and E3,
Failsafe mode off
Off by E3
Error LED lights up at errors of error classes E1 and E2,
Failsafe mode off
On +Failsafe
Error LED lights up at errors of all error classes, Failsafe
mode on *)
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31
3ADR010278, 3, en_US
565