Section 2 Installation
Cables
3BSE 027 941 R301
45
•
Other requirements:
–
Room lighting independent of the equipment power source. A battery-
powered emergency lighting system is recommended.
–
A well-developed process connection, with or without marshalling
facilities.
–
Effective grounding through a net of copper bars
–
Cable routing observing standard installation regulations.
–
Availability of power and other necessary utilities.
–
Observation of standards and legal regulations.
–
Sufficient free space in front of the cabinet in order to fully open the
doors. For safety reasons there must always be adequate space available,
even with the doors in the fully open position.
For additional information regarding design considerations, see
Electro-Magnetic Compatibility
The AC 800M units are intrinsically EMC compatible according to CE marking
rules. For additional information regarding Electro-Magnetic Compatibility,
see
Appendix D, Directive Considerations
Cables
Laying Field Cables
There are no special requirements for laying field and communication cables
connected to AC 800M. However:
•
Cables for short-distance communication without modems should always be
routed at a distance of 10 cm (4 in) from other cables.
•
All cables connected to AC 800M should be routed at a distance of 30cm
(12 in) from all power cables and 10 cm (4 in) from cables belonging to the
relevant international immunity standard, class 4.
Содержание AC 800M
Страница 1: ...ControlIT AC 800M Version 2 1 Controller Hardware Hardware and Operation...
Страница 2: ......
Страница 3: ...Controller Hardware Hardware and Operation ControlIT AC 800M Version 2 1...
Страница 10: ...7DEOH RI RQWHQWV 10 3BSE 027 941 R301...
Страница 20: ...Related Documentation About This Book 20 3BSE 027 941 R301...
Страница 26: ...Operating Environment Safety Summary 26 3BSE 027 941 R301...
Страница 42: ...Product Release History Section 1 Introduction 42 3BSE 027 941 R301...
Страница 108: ...Powering from an External 24 V DC Source Section 3 Configuration 108 3BSE 027 941 R301...
Страница 118: ...Verification of Redundant CPU Section 4 Operation 118 3BSE 027 941 R301...
Страница 212: ...Low Voltage Directive LVD Appendix D Directive Considerations 212 3BSE 027 941 R301...
Страница 214: ...Hazardous Location Approval Appendix E Standards 214 3BSE 027 941 R301...
Страница 228: ...QGH 228 3BSE 027 941 R301...
Страница 229: ......