Data
Value
Program change
07KT94-ARC-AD: 907 PC 331
07KT98-ARC-AD: Automation Builder
Man-Machine Communication
Yes, e.g. via Automation Builder
Electrical isolation
Potential differences
In order to avoid potential differences between
the replacement device 07KT98-AD and the
peripheral devices connected to COM2, these
devices are supplied by the socket in the
switchgear cabinet.
Terminal assignment and description of the
COM2 interface
Chapter 1.4.1.3.1.11 “Serial interface
For further information, please refer to the existing documentation
System description Advant Controller 31.
Data
Value
Programming
07KT94-ARC-AD: 907 PC 331
07KT98x-AD: Automation Builder
Program change
07KT94-ARC-AD: 907 PC 331
07KT98x-AD: Automation Builder
Electrical isolation
No
Connection to the CS31 bus
When configuring the CS31 bus interface (connector X5), select the COM1 interface of CPU
PM590 in Automation Builder.
The shield connection must be internally connected to FE.
Data
Value
Interface standard
EIA RS-485
Connection:
-> as master PLC
Yes
-> as slave PLC
No
Setting of the CS31 bus module address
No, the master has no module address
Electrical isolation
Yes
Terminal assignment and description of the
CS31 bus interface
Chapter 1.4.1.3.1.3 “Connection for CS31
Note that the shield connection is internally
connected to FE.
Serial interface
DIAG
AC31 Adapters
Replacement devices: CPU > Replacement device 07KT9x-AD
2018/09/24
3ADR010122, 8, en_US
52