Table 54: CS31 bus
Type
Byte
Connector / Terminal
WORD input (send) 0
1
X2 / 2.1, X2 / 2.0
2
WORD input (send) 1
3
X2 / 2.3, X2 / 2.2
4
WORD input (send) 2
5
X2 / 2.5, X2 / 2.4
6
WORD input (send) 3
7
X3 / 2.7, X3 / 2.6
8
WORD input (send) 4
9
X5 / 4.1, X5 / 4.0
10
WORD input (send) 5
11
X5 / 4.3, X6 / 4.2
12
WORD input (send) 6
13
X6 / 4.5, X6 / 4.4
14
WORD input (send) 7
15
X6 / 4.7, X6 / 4.6
16
When the measuring values are bipolar, use data type "INT input" instead of
"WORD input".
1.5.3.2.6 Behavior during normal operation
Interpretation of the LEDs:
● The device initializes automatically after the supply voltage is switched on. During this time,
the S-ERR LED flashes.
● The PWR LED lights up as soon as the internal supply voltage of the device is present.
● After successful initialization of the I/O bus communication to the S500 module, the I/O bus
LED lights up.
● After successful initialization of the CS31 bus communication, the CS31 bus LED lights up.
The S-ERR LED goes out.
● During operation, the yellow LEDs indicate the signal statuses of the channels.
The RAM is checked during the initialization of the device. In addition, the firmware in the Flash
memory is checked by means of a checksum during initialization. When the control system
(PLC/central unit) is stopped during normal operation, the inputs remain active.
1.5.3.2.7 Diagnosis and display
LEDs are used for diagnosis and display purposes. In addition, some diagnosis information can
be transmitted via the CS31 bus.
AC31 Adapters
Replacement devices: I/O modules > Replacement device 07AI91-AD
2018/09/24
3ADR010122, 8, en_US