Section 20
IED and functionality tests
20.1
Electromagnetic compatibility tests
Table 569:
Electromagnetic compatibility tests
Description
Type test value
Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
•
Common mode
2.5 kV
•
Differential mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
•
Contact discharge
8 kV
•
Air discharge
15 kV
Radio frequency interference
tests
•
Conducted, common mode 10 V (emf), f=150 kHz...80 MHz
IEC 61000-4-6 , level 3
IEC 60255-22-6
•
Radiated, amplitude-
modulated
20 V/m (rms), f=80...1000 MHz
and f=1.4...2.7 GHz
IEC 61000-4-3, level 3
IEC 60255-22-3
ANSI C37.90.2-2004
Fast transient disturbance tests
IEC 61000-4-4
IEC 60255-22-4, class A
ANSI C37.90.1-2012
•
Communication ports
4 kV
•
Other ports
4 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-22-5
•
Communication
1 kV line-to-ground
•
Other ports
2 kV line-to-ground, 1 kV line-to-
line
•
Power supply
4 kV line-to-ground, 2 kV line-to-
line
Table continues on next page