Table 483:
PRPSTATUS Output signals
Name
Type
Description
LAN1-A
BOOLEAN
LAN1 channel A status
LAN1-B
BOOLEAN
LAN1 channel B status
16.10.4
Setting parameters
The PRPSTATUS function has no user settings.
However, the redundant communication is configured in the LHMI under
Main menu/
Configuration/Communication/TCP-IP configuration/ETHLAN1_AB
where
Operation mode
,
IPAddress
and
IPMask
are configured.
16.11
Activity logging parameters ACTIVLOG
16.11.1
Activity logging ACTIVLOG
ACTIVLOG contains all settings for activity logging.
There can be 6 external log servers to send syslog events to. Each server can be configured
with IP address; IP port number and protocol format. The format can be either syslog
(RFC 5424) or Common Event Format (CEF) from ArcSight.
16.11.2
Settings
Table 484:
ACTIVLOG Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ExtLogSrv1Type
Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP
-
-
Disabled
External log server 1 type
ExtLogSrv1Port
1 - 65535
-
1
514
External log server 1 port number
ExtLogSrv1IP
0 - 18
IP
Address
1
127.0.0.1
External log server 1 IP-address
ExtLogSrv2Type
Disabled
ExtLogSrv1Type
SYSLOG TCP/IP
CEF TCP/IP
-
-
Disabled
External log server 2 type
ExtLogSrv2Port
1 - 65535
-
1
514
External log server 2 port number
ExtLogSrv2IP
0 - 18
IP
Address
1
127.0.0.1
External log server 2 IP-address
Table continues on next page
Section 16
1MRK 502 048-UUS A
Station communication
658
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...