Table 256:
DB_LINE (3) Output signals
Name
Type
Description
989REL
BOOLEAN
Switching of 989 is allowed
989ITL
BOOLEAN
Switching of 989 is not allowed
389GREL
BOOLEAN
Switching of 389G is allowed
389GITL
BOOLEAN
Switching of 389G is not allowed
989GREL
BOOLEAN
Switching of 989G is allowed
989GITL
BOOLEAN
Switching of 989G is not allowed
12.3.8.6
Settings
The function does not have any settings available in Local HMI or Protection and Control
IED Manager (PCM600).
12.3.9
Interlocking for line bay ABC_LINE (3)
12.3.9.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Interlocking for line bay
ABC_LINE
-
3
12.3.9.2
Functionality
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a
double busbar arrangement with a transfer busbar according to figure
can also be used for a double busbar arrangement without transfer busbar or a single
busbar arrangement with/without transfer busbar.
1MRK 502 048-UUS A
Section 12
Control
425
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...