12.2.5.4
Signals
Table 223:
QCBAY Input signals
Name
Type
Default
Description
LR_OFF
BOOLEAN
0
External Local/Remote switch is in Off position
LR_LOC
BOOLEAN
0
External Local/Remote switch is in Local position
LR_REM
BOOLEAN
0
External Local/Remote switch is in Remote position
LR_VALID
BOOLEAN
0
Data representing the L/R switch position is valid
BL_UPD
BOOLEAN
0
Steady signal to block the position updates
BL_CMD
BOOLEAN
0
Steady signal to block the command
Table 224:
QCBAY Output signals
Name
Type
Description
PSTO
INTEGER
Value for the operator place allocation
UPD_BLKD
BOOLEAN
Update of position is blocked
CMD_BLKD
BOOLEAN
Function is blocked for commands
LOC
BOOLEAN
Local operation allowed
REM
BOOLEAN
Remote operation allowed
12.2.5.5
Settings
Table 225:
QCBAY Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
AllPSTOValid
Priority
No priority
-
-
Priority
Priority of originators
12.2.6
Local remote LOCREM
12.2.6.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Local remote
LOCREM
-
-
12.2.6.2
Functionality
The signals from the local HMI or from an external local/remote switch are applied via the
function blocks LOCREM and LOCREMCTRL to the Bay control QCBAY function
Section 12
1MRK 502 048-UUS A
Control
368
Technical manual
Содержание 650 series
Страница 1: ...Relion 650 series Generator protection REG650 ANSI Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 62: ...56 ...
Страница 68: ...62 ...
Страница 156: ...150 ...
Страница 198: ...192 ...
Страница 512: ...506 ...
Страница 644: ...638 ...
Страница 714: ...708 ...
Страница 777: ...771 ...