Table 131:
GUPPDUP (37) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
Mode
A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
-
-
Pos Seq
Mode of measurement for current and voltage
8.7.3.5
Monitored data
Table 132:
GUPPDUP (37) Monitored data
Name
Type
Values (Range)
Unit
Description
P
REAL
-
MW
Active Power
PPERCENT
REAL
-
%
Active power in % of
calculated power base value
Q
REAL
-
MVAr
Reactive power
QPERCENT
REAL
-
%
Reactive power in % of
calculated power base value
8.7.4
Operation principle
A simplified scheme showing the principle of the power protection function is shown in
figure
. The function has two stages with individual settings.
Section 8
1MRK 502 048-UUS A
Current protection
258
Technical manual