1MAC050144-MB C
Section 10
Other functions
615 series ANSI
623
Technical Manual
10.5.4
Settings
Table 533: TONGAPC Non group settings
10.5.5
Technical data
Table 534: TONGAPC Technical data
Parameter
Values (Range) Unit Step Default Description
On delay time 1
0...3600000
ms
10
0
On delay time
On delay time 2
0...3600000
ms
10
0
On delay time
On delay time 3
0...3600000
ms
10
0
On delay time
On delay time 4
0...3600000
ms
10
0
On delay time
On delay time 5
0...3600000
ms
10
0
On delay time
On delay time 6
0...3600000
ms
10
0
On delay time
On delay time 7
0...3600000
ms
10
0
On delay time
On delay time 8
0...3600000
ms
10
0
On delay time
Characteristic
Value
Operate time
accuracy
±1.0% of the set
value or ±20 ms
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......