1MAC050144-MB C
Section 7
Control functions
615 series ANSI
497
Technical Manual
The synchronism requirement for the CBBs can be defined with the
Synchronisation set
setting, which is a bit mask. The lowest bit in the
Synchronisation set
setting is related to
CBB1 and the highest bit to CBB7. For example, if the setting is set to "1", only CBB1
requires synchronism. If the setting is it set to "7", CBB1, CBB2 and CBB3 require the
SYNC
input to be TRUE before the reclosing command can be given.
Figure 269:
Initiation during discrimination time - AR function goes to lockout
The discrimination time starts when the close command
CLOSE_CB
has been given. If a
pickup input is activated before the discrimination time has elapsed, the AR function goes
to lockout. The default value for each discrimination time is zero. The discrimination time
can be adjusted with the
Dsr time shot 1…4
parameter.
Figure 270:
Initiation after elapsed discrimination time - new shot begins
7.2.4.5
Sequence controller
When the
LOCKED
output is active, the AR function is in lockout. This means that new
sequences cannot be initialized, because AR is insensitive to initiation commands. It can
be released from the lockout state in the following ways:
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......