Section 4
1MAC050144-MB C
Protection functions
284
615 series ANSI
Technical Manual
Table 283: 32P non-group settings
4.4.1.8
Monitored data
Table 284: 32P Monitored data
4.4.2
Ground directional power protection
Directional negative/zero sequence power protection (32N) is used to detect the direction
of negative sequence power or residual power.
Release signal is given if the angle difference between polarizing and operating quantity
is in predefined direction (forward or reverse direction). The release signal is given with a
definite time delay.
4.4.2.1
Identification
Name
Values (Range) Unit Step
Default Description
Operation
0=Off
1=On
1=ON
Operation Off / On
Reset delay time
0…60000
ms
1
20
Reset delay time
Min trip voltage
0.01…1.00
pu
0.01
0.3
Minimum operating voltage
Min trip current
0.005…1.00
pu
0.001
0.1
Minimum operating current
Name
Type
Values (Range)
Unit
Description
DIRECTION
ENUM
0=unknown
1=forward
2=backward
Direction information
ANGLE_RCA
REAL
Angle between operating angle and characteristic angle
Functional description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional negative/zero sequence power
protection
DNZSRDIR
Q>->
32N
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......