4.1.12.9
Technical data
Table 215: 51LR Technical data
4.1.13
Loss of Phase, 37
4.1.13.1
Identification
Table 216: Function identification
4.1.13.2
Function block
Figure 103:
Function block symbol
4.1.13.3
Functionality
The phase undercurrent protection 37 is used to detect an undercurrent which is considered
as a fault condition.
37 starts when the current is less than the set limit. Operation time characteristics are
according to definite time (DT).
The function contains a blocking functionality. It is possible to block function outputs and
reset the definite timer if desired.
Characteristic
Value
Pickup accuracy
Depending on the frequency of the current
measured: f
n
±2Hz
±1.5% of the set value or ±0.002 x I
n
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 35 ms
Trip time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase undercurrent protection
PHPTUC1
3I<
37
I_A
I_B
OPERATE
I_C
BLOCK
START
OPR_A
OPR_B
OPR_C
ST_A
ST_B
ST_C
PHPTUC1
Содержание 615 Series ANSI
Страница 1: ...Relion Protection and Control 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 29: ...1MAC050144 MB C Section 615 series ANSI 22 Technical Manual ...
Страница 389: ...Section 4 1MAC050144 MB C Protection functions 382 615 series ANSI Technical Manual ...
Страница 485: ...Section 6 1MAC050144 MB C Supervision functions 478 615 series ANSI Technical Manual ...
Страница 635: ...Section 10 1MAC050144 MB C Other functions 628 615 series ANSI Technical Manual ...
Страница 707: ...Section 15 1MAC050144 MB C Applicable standards and regulations 700 615 series ANSI Technical Manual ...
Страница 711: ...Section 16 1MAC050144 MB C Glossary 704 615 series ANSI Technical Manual ...
Страница 712: ......