Operating instruction

IM/695FI_8

600T EN Series

Model 695FI

Field Indicator

ASEA BROWN BOVERI

Содержание 600T Series

Страница 1: ...1 Operating instruction IM 695FI_8 600T EN Series Model 695FI Field Indicator ASEA BROWN BOVERI...

Страница 2: ...his manual is intended only to assist our customers in the efficient operation of our equipment Use of this manual for any other purpose is specifically prohibited and its contents are not to be repro...

Страница 3: ...tes shown below The Nameplate provides information concerning the product code theinputsignal theproductserialnumber seeRef A Please refer to this number when making enquiries The Safety Marking plate...

Страница 4: ...ter s terminal block fig 3 2 Junction box i e inserted in any point of the 4 to 20 mA line connecting the transmitter to its receiver power supply fig 4 In any cases the line resistance to the field i...

Страница 5: ...EMOTE METER M Fig 3 Fig 4 To receiver power supply To receiver power supply 695FI as indicator only 695FI as junction box 2600T transmitter terminal block 2600T transmitter terminal block Fig 3a Fig 4...

Страница 6: ...y in place screw on the cover and tighten WARNING ForHazardousAreasinstallations the connection of cables and conduits to the indicator shall be made in accordance with the requirements of the relevan...

Страница 7: ...r itself and the transmitter can be configured ProMeter is only programmable In fact two are the main menu ConF METER and ConF XMTR ACCESS TO CONFIGURATION To enter these men for both indicators the k...

Страница 8: ...itterconnected Before accepting the transmitter configuration by pressing ENTERattherequest ConFUPDATE itispossibletoview the LRV ZERO the URV FULL SC and the UNIT If the output transfer function of t...

Страница 9: ...g the transmitter information See below a list of the available operation under the selected option CONF menu TRIM menu REVIEW menu PV menu Change LRV Reranging RERANG TAG 8 Primary variable PRIMARY C...

Страница 10: ...UT 12000 OUT mA ENTER MANUAL ENTER SET 4mA ENTER 04 000 04 000 04 000 04 000 04 000 REF V AL 4 000 REF TX ENTER SET20 mA ENTER ENTER 20 000 20 000 20 000 20 000 20 000 REF V AL 20 000 REF TX ENTER ENT...

Страница 11: ...ESC 0 000 LR V ESC 40 000 UR V ESC 40 000 LRL ESC 40 000 URL ESC 1 0000 DAMPING ESC OUTPUT LIN ESC ENTER ESC NEXT PREV NEXT PREV Fig 11 PV menu ENG UNITS PV ENTER PRIMAR Y ESC ENTER 10 sec 10 690 KP A...

Страница 12: ...max span 16 mA EMI RFI Total effect 0 10 from 20 to 1000 MHz and for field strengths up to 10 V m when instrument is properly in stalled Input range 4 to 20 mA nominal Operating range 3 6 to 22 mA for...

Страница 13: ...certificate number 01ATEX015 The meaning of ATEX code is as follows II Group for surface areas not mines 1 or 2 Category G Gas dangerous media D Dust dangerous media T50 C Maximum surface temperature...

Страница 14: ...he number close to the CE marking of the indicator safety label identifies the Notified Body which carries out the Surveillance for the production of the indicator The other marking refers to the prot...

Страница 15: ...surement Also liquid level and temperature I to P Converters and Field Indicators Flow Metering Magnetic Flowmeters Electromagnetic insertiontypeprobesandwatermeters Turbine Flowmeters Wedge Flow Elem...

Страница 16: ...Ltd Howard Road St Neots Cambridgeshire PE19 3EU UK Tel 44 0 1480 475321 Fax 44 0 1480 217948 ABB Inc 125 E County Line Road Warminster PA 18974 USA Tel 1 215 674 6000 Fax 1 215 674 7183 ABB SpA Meas...