80
Configuring the 56/64 kbit data
communication modules
&KDSWHU
,QVWDOODWLRQRIWKHRSWLFDOFDEOHVLQ
WHUPLQDOVDQGFXELFOHV
7DEOH 6XPPDU\
1R &20)$,/WULJJHULQJ
&20)$,/WULJ
JHULQJWLPH
'URSRXW
GHOD\PV
5HPDUN
1
Transmit error
≥
50 ms
Messages can not be sent
2
Receive error
≥
100 ms
No valid messages received
3
Block differential protection
0 ms
Block of the differential protection due to
setting changes etc.
4
Remote terminal COMFAIL
0 ms
COMFAIL from the remote terminal. For
error no 1, 2, 3, and no 5, 6, 7, 8, 9, 10
the COMFAIL is sent in the second con-
secutive message (within 10 ms)
5
Time synchronization error
≥
2 s
Problems in the synchronization of inter-
nal differential clock in the differential
protection. The clock refers to the syn-
chronized counters 0-39999
µ
s in each
terminal. The clock is independent of
the real time clock in the terminal.
6
Differential clock drift
> 0 ms
Unacceptable drift of the internal differ-
ential clock in the slave terminal com-
pared to the internal differential clock in
the master terminal (slave- master -
slave)
7
Communication channel
loop delay - instantaneous
0 ms
Checks if the loop time (slave - master -
slave) in the differential communication
channel 31 ms
8
Communication channel
loop delay - time delayed
≥
2 s
Checks if the loop time (local - remote-
local) in the differential communication
channel 24 ms
9
Abnormal clock deviation
0 ms
Internal differential clock deviation
(slave- master - slave)
10
Data flow
2QO\LQYHUVLRQ
0 ms
Long time between attempts to send
messages and adjustment of the real
time terminal clock . The terminal clock
is the real time clock in the terminal for
time tagging of events etc.