73
Technical data
EN
10.2 Cable specifications
EVSE
Terra 60
Terra 360
AC Input
AC cable cross section
150 mm
2
(recommend)
2 x 240 mm
2
(recommend)
AC connection type
M10 cable lug
M12 cable lug
AC cable diameter (cable entry plate)
27...35 mm
Max. 34 mm
Protective Earth (PE)
PE cable cross section
At least half of the phase cable cross section
PE connection type
M10 cable lug
PE cable diameter (cable entry plate)
19...28 mm
27...35 mm
PE connection point
2 on the PE busbar
Ethernet
CAT
CAT 5e (recommend)
CAT 6 (high presence of electromagnetic
interference and/or noise)
Ethernet cable diameter (cable entry plate)
8...13 mm
19...28 mm
Tilt sensor (option)
Number of wires
4 (2 wires for power supply and 2 wires for relay
contacts)
Max. Wires cross section
4mm
2
Diameter outside
Cable diameter accepted by cable gland:
19...28 mm
Conductor
Fine strand copper wire
Insultation
PVC or other material that is serviceable for
outdoor use and UV-protected
Voltage rating
600 V
10.3 Torque specification
EVSE
Terra 60
Terra 360
Parameter
Specification [Nm]
Specification [Nm]
Fasteners for the PE wire
50...55
Fasteners for the L1, L2, L3 (neutral wire Terra 60)
30...44
50...75
Fasteners for the connection of the EVSE to the base
(M12 bolt)
10
Tilt sensor screw terminal block
3