Chapter
7
7-1
Module Calibration
In this chapter we tell you how to calibrate your module.
To calibrate your analog module, you will need the following tools and
equipment:
Tool or Equipment
Description
Precision Voltage Source
0-10V, 1
µ
V resolution
Precision Multimeter
25mA, 1
µ
A resolution
10V, 1
µ
V resolution
Programming Terminal
and Interconnect Cable
Programming terminal for A-B family processors
Your analog module is shipped already calibrated from the factory. To
recalibrate the module, it must be able to communicate with the processor
and a programming terminal.
If the processor has block transfer capability, you must enter ladder logic
into the processor memory before calibrating the module. You can then
initiate BTWs to the module, and the processor can read inputs from the
module (BTRs).
Table 7.A
Calibration Block Transfer Write Data File or Discrete Output Data File
Discrete Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Discrete Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word 0
1
1
0
0
WR
IM
EX
HL
O1
O0
I3
I2
I1
I0
Word 1
Output Channel 0 Calibration Data
Word 2
Output Channel 1 Calibration Data
Chapter Objective
Tools and Equipment
Calibrating your Module