ControlLogix™ AC (74-265V) Output Module
9
Publication
1756-IN028D-EN-P - February 2003
Wire the Module
You can only connect wiring to your module through an RTB or IFM.
The example below shows how to wire the module.
After completing field-side wiring, secure the wires in the strain relief
area with a cable-tie.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
40175-M
L1
L2
Daisy chain
to other
RTBs
1756-OA16
Group 0
Group 0
Group 1
Group 1
1.
This wiring example shows a single voltage source.
2.
When you daisy chain from a group to other RTBs, always connect the daisy chain
as shown. Do not connect more than 2 wires to any single terminal at any time.
3.
If separate power sources are used, do not exceed the specified isolation voltage.
OUT-1
OUT-3
OUT-5
OUT-7
OUT-9
OUT-11
OUT-13
OUT-15
L1-0
L1-1
OUT-0
OUT-2
OUT-4
OUT-6
OUT-8
OUT-10
OUT-12
OUT-14
L2-0
L2-1
NOTES:
Содержание 1756-ENBT ControlLogix
Страница 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Страница 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Страница 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Страница 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...