38
RSM-DEV1 Technical Guide
APPENDIX A: VFD CONFIGURATION
Yaskawa V1000 Configuration
In order for the module to communicate with the Yaskawa V1000,
it needs to be configured to the following settings. For more
information, refer to the Yaskawa
V1000 Technical Manual
.
b1-01 = 2: MEMOBUS communications
b1-02 = 2: MEMOBUS communications
H5-01 Drive Slave Address
Default = 31 (1F)
H5-02 Comm Speed
Default = 3: 9600
H5-03 Comm Parity
Default = 0: No Parity
H5-04 Stop Method after comm error
Default = 1: Coast to stop
H5-05 Comm Fault Detection
Default = 1 Enabled to fault on comm loss
H5-06 Drive transmit wait time
Default = 5 ms
H5-07 RTS Control Selection
Default = 1: Enabled – RTS Switches while sending
H5-09 CE Detection Time
NOT Default: Set to 10.0 seconds