51
Adjustable Fan Cycling Switch Procedure
To adjust the fan cycle switch you will need a
flathead screwdriver.
Recommended Settings
The switch will come factory set to cut-in at
2.93 Mpa [425psi] (+/– 5psi) and a
differential of 1.69 Mpa [155psi] (or open at
1.86 Mpa [270psi] (+/– 5psi)).
Note: 5 psi = 34.5 kpa
Settings for CUT IN and DIFFERENTIAL
PRESSURE are indicated with two slider
gauges.
Each adjustment screw sits above the setting
that it controls.
Cut In
Differential