94
Electric Preheat
Figure 54 - Preheat Controller
The electric preheat controller is factory
installed within the preheat cabinet. The
following details are for EHC1 version 1.10
of the preheat controller.
Status Display Screens
These screens are access by pressing either
the left or right controller buttons and
scrolling through the following displays.
1.
LAT
- Measured leaving air temperature
(LAT), average of LAT A and B probes.
MOD
- Modulation rate % currently
being applied to stage one SCR.
2.
WKGset
- "Working" LAT setpoint (°F)
(LATeet>>RESETset as adjusted by 0-
10V RESET signal).
3.
LATset
- Leaving air temperature (°F)
control setpoint.
4.
RESETset
- "Reset" air temperature (°F)
control setpoint.
5.
OATset
- Outside air temperature (°F)
control
setpoint,
measured
outside
temperature must be less to enable
preheat.
6.
LLTset
- “Low Limit Time” temperature
(°F) setpoint. If this temperature is not
reached at full output, relay will pull in.
7.
Stage
- Current operating stage 1-6.
8.
Stage
- Current operating stage 1-6.
MOD
- Modulation rate % being applied
to stage one heat strip SCR.
Flash Code LED
Screen
Controller
Buttons
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Страница 36: ...36 Figure 9 Steel Mounting ...
Страница 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Страница 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Страница 129: ...Maintenance Log E Coated Coil ...