
93
Should overheating occur with a gas heat
exchanger, or the gas supply fail to shut off,
shut off the manual gas valve to the furnace
before shutting off the electrical supply.
Prolonged overheating of the heat exchanger
will shorten its life.
If unit has not been selected as a 100%
outside air unit (makeup air unit) the return
air duct must be sealed to the unit and the
return air temperature must be maintained
between 55
F and 80
F.
Table 27 - Electric and Gas Heating Capacities
Model Option
B2
Gas Heat
Electric Heat
Input Capacity
Output Capacity
Capacity
MBH
MBH
kW (208V)
kW (230V,
380V 460V,
575V)
1
=
Heat 1
7.5
10
2
=
Heat 2
90.0
72.0
15.0
20
3
=
Heat 3
22.5
30
4
=
Heat 4
270.0
218.7
30.0
40
5
=
Heat 5
37.5
50
6
=
Heat 6
390.0
315.9
45.1
60
7
=
Heat 7
60.1
80
8
=
Heat 8
405.0
328.1
75.1
100
9
=
Heat 9
90.1
120
A
=
Heat A
120.1
160
B
=
Heat B
150.2
200
C
=
Heat C
540.0
432.0
180.2
240
D
=
Heat D
810.0
648.0
210.3
280
E
=
Heat E
1080.0
864.0
240.3
320
F
=
Heat F
195.0
156.0
G
=
Heat G
292.5
234.0
K
=
Heat K
150.0
120.0
L
=
Heat L
210.0
168.0
M =
Heat M
800.0
640.0
N =
Heat N
1600.0
1280.0
P =
Heat P
2400.0
1920.0
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Страница 36: ...36 Figure 9 Steel Mounting ...
Страница 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Страница 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Страница 129: ...Maintenance Log E Coated Coil ...