75
Removal
Take off the fan grill by removing the screws
that attach it to the orifice.
The condenser fan motor wires can then be
accessed and disconnected.
Remove the screws that attach the orifice to
the condenser assembly. The screws are
located on the top of the orifice around the
perimeter, and in some cases, through the
side of the condenser assembly into the
orifice.
With the wires disconnected and the screws
removed, the fan, motor and orifice assembly
can be lifted off the unit.
Figure 46 - Removal of a Condenser Fan
Assembly
Reinstallation
Set the condenser fan, motor and orifice
assembly back into the condenser assembly
with the motor wires on the side closest to the
control panel.
Attach the orifice to the condenser assembly
using all of the points where screws were
removed.
Reconnect the fan motor wires.
Attach the fan grill at all of the points where
screws were removed.
Suction Filter (55, 65 and 75-140 ton)
In an effort to help protect the compressors
from contaminants during testing and startup,
AAON is now factory installing pleated
replaceable core suction line filters on the
RNE Series products (55, 65, and 75-140
tons)
Figure 47 - RPE-48-BD filter element
One month after startup, remove the RPE-48-
BD filter element for the lowest possible
pressure drop. Removing the suction line
filter will improve the efficiency and capacity
of the unit. AAON installs isolation ball
valves on both sides of the suction line filter
Improper
installation,
adjustment,
alteration, service, or maintenance
can cause property damage, personal
injury, or loss of life. Startup and
service must be performed by a
Factory Trained Service Technician.
WARNING
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Страница 36: ...36 Figure 9 Steel Mounting ...
Страница 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Страница 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Страница 129: ...Maintenance Log E Coated Coil ...