123
Appendix B - Thermistor Temperature vs. Resistance Values
Deg C
Deg F
Resistance (kOhms)
-40
-40
2889.6
-35
-31
2087.22
-30
-22
1522.20
-25
-13
1121.44
-20
-4
834.72
-15
5
627.28
-10
14
475.74
-5
23
363.99
0
32
280.82
5
41
218.41
10
50
171.17
15
59
135.14
20
68
107.44
25
77
86.00
30
86
69.28
35
95
56.16
40
104
45.81
45
113
37.58
50
122
30.99
55
131
25.68
60
140
21.40
65
149
17.91
Deg C
Deg F
Resistance (kOhms)
70
158
15.07
75
167
12.73
80
176
10.79
85
185
9.20
90
194
7.87
95
203
6.77
100
212
5.85
105
221
5.09
110
230
4.45
115
239
3.87
120
248
3.35
125
257
2.92
130
266
2.58
135
275
2.28
140
284
2.02
145
293
1.80
150
302
1.59
155
311
1.39
160
320
1.25
165
329
1.12
170
338
1.01
175
347
0.92
180
356
0.83
Содержание RN Series
Страница 2: ......
Страница 32: ...32 Figure 5 RN Series 6 8 and 10 ton Unit Isolator Locations ...
Страница 33: ...33 Figure 6 RN Series 9 and 11 15 ton Unit Isolator Locations ...
Страница 34: ...34 Figure 7 RN Series 16 25 and 30 ton Unit Isolator Locations ...
Страница 35: ...35 Figure 8 RN Series 26 31 50 60 and 70 ton Unit Isolator Locations ...
Страница 36: ...36 Figure 9 Steel Mounting ...
Страница 102: ...102 Figure 56 Example 6 50 60 70 ton through the Base Gas Piping ...
Страница 105: ...105 Gas Heater Operating Instructions Figure 58 Gas Heater Instructions ...
Страница 129: ...Maintenance Log E Coated Coil ...