MODGAS-XWR2-B Technical Guide
WIRING
Important Wiring Considerations
Wiring
The modules must be connected to an 18-30 VAC power source
of the proper size for the calculated VA load requirements. All
transformer sizing should be based on the VA ratings listed in
Table
1, this page
.
NOTE:
If the temperature at the MODGAS-XWR2-B is below
-4ºF (-20ºC), the display refresh rate could be less
responsive.
WARNING:
When using a single transformer to power
more than one controller or expansion module,
the correct polarity must always be maintained
between the boards. Failure to observe correct
polarity will result in damage to the AAON
unit controller, MODGAS-XWR2-B, and any
associated module.
Please carefully read and apply the following information when
wiring the AAON unit controller, MODGAS-XWR2-B and any
associated module.
1. All wiring is to be in accordance with local and national
electrical codes and specifications.
2. All 24 VAC wiring must be connected so that all ground
wires remain common. Failure to follow this procedure
can result in damage to the controller and connected
devices.
3.
Minimum wire size for 24 VAC wiring should be
18-gauge.
4. Minimum wire size for all sensors should be 24-gauge.
Some sensors require two-conductor wire and some
require three-or four-conductor wire.
5. Minimum wire size for 24 VAC thermostat wiring should
be 22-gauge.
6. Be sure that all wiring connections are properly inserted
and tightened into the terminal blocks. Do not allow wire
strands to stick out and touch adjoining terminals which
could potentially cause a short circuit.
7. When communication wiring is to be used to interconnect
AAON unit controllers together or to connect to other
communication devices, all wiring must be plenum-
rated, minimum 18-gauge, two-conductor, twisted-pair
with shield. AAON can supply communication wire that
meets this specification and is color coded for the network
or local loop. Please consult your AAON distributor for
information. If desired, Belden #82760 or equivalent wire
may also be used.
8.
Before applying power to the AAON unit controller,
MODGAS-XWR2-B, and any associated modules, be
sure to recheck all wiring connections and terminations
thoroughly.
Powering Up
When the controller and modules are first powered up, the POWER
LED should light up and stay on continuously. If it does not light up,
check to be sure that you have 24 VAC connected to the controller,
that the wiring connections are tight, and that they are wired for the
correct polarity. The 24 VAC power must be connected so that all
ground wires remain common. If after making all these checks, the
POWER LED does not light up, please contact AAON Controls
Support for assistance.
Control
Device
Voltage
VA
Load
Operating Temperature
Humidity
(Non-
Condensing)
MODGAS-XWR2-B
18-30 VAC
18
-22°F to 158°F
-30ºC to 70ºC
0-95% RH
Inputs
Resistive Inputs require 10KΩ
Type III Thermistor
24 VAC Inputs provide 4.7KΩ
Load
Outputs
Relay Outputs: 1 amp
maximum per output.
Table 1: Electrical and Environmental Requirements