24
MODGAS-X Technical Guide
LCD SCREENS
Setpoint and Force Screens
Setpoint Screens
Refer to the following map when navigating through the Setpoint
Screens. From the SETPOINTS Screen, press
<ENTER>
to
scroll through the screens and change setpoints. Use the
<UP>
and
<DOWN>
arrow keys to change your selections. Then press
<ENTER>
to save the new setpoint.
NOTE:
When the MODGAS-X Module is operating in
Communications Mode, these setpoint screens
will not appear on the LCD display because they
are controlled by the AAON unit controller.
SET
POINTS
SAT SP
40-200°F
HEATING SUPPLY AIR TEMPERATURE SETPOINT
This is the target temperature while the heating is enabled. If you are
using the reset signal, this is the setpoint it will calculate to at zero
volts. Will display only in Stand-Alone Mode.
The SAT Setpoint is set by the LCD Display in Stand-Alone Mode
and is set by the AAON unit controller in Communications Mode.
Minimum
Default
Maximum
40ºF
120ºF
200ºF
5ºC
49ºC
93ºC
RESET SP
40-200°F
RESET HEATING SUPPLY AIR SETPOINT
This is the maximum temperature at which the Supply Air Temperature
will reset to. It will only display in Stand-Alone Mode.
The Reset Setpoint is set by the LCD Display in Stand-Alone Mode and
is set by the AAON unit controller in Communications Mode.
Minimum
Default
Maximum
40ºF
120ºF
200ºF
5ºC
49ºC
93ºC
Force Screens
Refer to the following map when navigating through the Force
Screens. From the FORCE Screen, press
<ENTER>
.
FORCE
VALVES
FORCE
MODE ON/OFF
Press the
<UP>
button to turn the Force Mode on.
Press the
<DOWN>
button to turn the Force Mode off.
FRC VALV
X%
FORCE VALVE PERCENTAGE
This screen only appears when Force Mode is on.
Press the
<UP>
button to increase the percentage.
Press the
<DOWN>
button to decrease the percentage
NOTE:
When you turn the Force Mode back off or after one hour has
elapsed, the valve will reinitialize to zero.
The next 15 screens are for relays only.
STAGE 1
MODULATING
This relay cannot be forced.
STAGE 2-14
FORCE ON
Press the
<UP>
button to turn the Force Relay on.
Press the
<DOWN>
button to turn the Force Relay off.
FORCE
TIMEOUT
FORCE MODE TIMEOUT
This screen will appear when the Force Mode times out after one
hour.