77
Pump Piping - General
The discharge valve only is to be used to
throttle pump flow, not the suction valve.
Care must be taken in the suction line layout
and installation, as it is usually the major
source of concern in centrifugal pump
applications
Alignment
Alignment is unnecessary on close-coupled
pumps as there is no shaft coupling.
Split-coupled units are accurately aligned at
the factory prior to being shipped and do not
need re-aligning when installed.
Pump Operation
Starting Pump
Ensure that the pump turns freely by hand, or
with some mechanical help such as a strap
and lever on larger pumps. Ensure that all
protective guarding is securely fixed in
position.
The pump must be fully primed on start up.
Fill the pump casing with liquid and rotate the
shaft by hand to remove any air trapped in the
impeller. On split coupled units, any air
trapped in the casing as the system is filled
must be removed by the manual air vent in
the seal flush line. Close-coupled units are
fitted with seal flush/vent lines piped to the
pump suction area. When these units operate
residual air is drawn out of the pump towards
the suction piping.
“Bump” or energize the motor momentarily
and check that the rotation corresponds with
the directional arrow on the pump casing. To
reverse rotation of a three phase motor,
interchange any two power leads.
Start the pump with the discharge valve
closed and the suction valve open, and then
gradually open the discharge valve when the
motor is at operating speed. The discharge
valve may be cracked” or open slightly at
start up to help eliminate trapped air.
When stopping the pump: Close the
discharge valve and de-energize the motor.
DO NOT run the pump against a closed
discharge valve for an extended period of
time. (A few minutes maximum)
Star-Delta motor starters should be fitted
with electronic/mechanical interlocks that
have a timed period of no more than 40
milliseconds before switching from star
(Starting) to delta (Run) connection yet allow
the motor to reach full star (Starting) speed
before switching to delta (Run).
Should the pump be noisy or vibrate on start-
up a common reason is overstated system
head. Check this by calculating the pump
operating head by deducting the suction
pressure gauge value from the discharge
gauge reading. Convert the result into the
units of the pump head as stated on the pump
nameplate and compare the values. Should
the actual pump operating head be
Use Caution. Piping may carry high
temperature fluid.
CAUTION
Discharge valve only is to be used to
throttle pump flow.
CAUTION
Do not run pumps with discharge
valve closed or under very low flow
conditions.
CAUTION
Содержание LZ Series
Страница 2: ......
Страница 27: ...27 Figure 6 Concrete Pad Mounting with Dimensions Figure 7 LZ Base ...
Страница 36: ...36 Figure 17 Typical Flue Vent Piping ...
Страница 40: ...40 Figure 24 Typical Vertical Vent Piping Figure 25 Vertical Termination of Air Intake and Vent Piping ...
Страница 83: ...83 ...
Страница 84: ...84 ...
Страница 95: ...95 Flo Trex Cross Section ...