35
Sidewall Direct Boiler Venting
For units with Lochinvar Knight XL and
SYNC boilers (feature B4 = A, B, C, D, E, F,
G, H, or K), the air intake and vent piping
runs from each boiler through the sidewall of
the unit into the supplied sidewall vent
termination.
1. On the sidewall above the boiler access
door, remove the shipping cover and attach
the sidewall vent plate shipped with the unit.
Figure 14 - Sidewall Vent Shipping Cover
Removal
Figure 15 - Sidewall Vent Plate Installation
2. Attach air intake piping to the air inlet
connector on the boiler at one end and run
through the sidewall of the unit at the other
end. All air intake pipes and fittings are
PVC.
Figure 16 - Typical Air Intake Piping
Use only primer and cement approved
for use with PVC (ANSI/ASTM
D2564).
WARNING