Typical Explosion Vent Installation.
To ensure proper installation of your explosion vent, carefully read the
separate manufacturer’s explosion vent installation guide.
WARNING: personal injury, death, and/or property damage can result from
material discharge during venting.
10.3
Explosion Vent Burst Sensor
All standard explosion vents come with a burst sensor. This can be
connected to an AAF Control Center or to the customer’s controls to shut down the
unit when an event occurs.
The magnetic sensor is suitable for use in Class I and II, Division I, Groups A
to G.
Under normal operation, when the disk is closed, the switch is closed. When
the disk opens, the switch opens (no electrical flow).
The connection cable is two wire, 3 feet long and has a voltage of 30VDC
and current of 10 mA. This cable will be wired on site.
To ensure proper installation of your explosion vent, carefully read the
separate manufacturer’s explosion vent installation guide.