EQUIPMENT OVERVIEW 

The AstroHood

 S-lll RSR Ducted HEPA Terminal Hood is a low-profile and lightweight, ducted 

room-side replaceable HEPA/ULPA filter terminal module of anodized aluminum construction using 
a gel seal minipleat or separator-less style filter pack. The Astrohood S-III RSR unit is designed to 
provide unidirectional airflow when installed in drywall or T-bar ceilings. AstroHood S-III RSR modules 
are available in three nominal sizes: 24”x24”, 24”x36”, and 24”x48”, for either 1-1/2” or 2” T-bar, and 
with 8”, 10”, 12”, or 14” diameter inlet collars.
The filter pack is sealed in an anodized extruded aluminum frame with integral gel seal channel to 
ensure an air-tight seal. The filter’s extruded aluminum center divider is furnished with a port for 
in-room baffle plate adjustment, and for measuring of an upstream challenge aerosol and static 
pressure. AAF Flanders does not recommend using the aerosol port as a means of aerosol injection.
The one-piece hood/inlet collar is made of spun aluminum, and the inlet collar is ribbed to secure the 
flex duct retaining strap. A 22-gauge, 40% open area removable perforated grille protects the media 
pack. Hanging holes (1/8" in diameter) are drilled on the module’s top four corners to secure seismic 
restraint wires or to hang the unit.

Unpacking

• Carefully remove the unit from the shipping carton and inspect for any damage that may have 

occurred during transportation. Two workers minimum are required to lift the unit from the 
container.

• Remove housing from shipping carton and inspect for concealed damage and any hardware that 

may have become loose in transit.

• Remove the Grille and Field Installed Trim, if supplied, and set aside. It is good practice to label or 

mark the grille and trim components to match with the respective unit to ensure good fitment.

Installation

Install and support housing as instructed on the following pages. Flexible duct connections should be 
made using stainless steel, worm-gear type draw bands for maximum reliability. Housing installation 
must be accomplished in a professional manner with flanges or trim properly sealed to prevent 
contaminant infiltration from the interstitial space.

Содержание AstroHood S-lll RSR

Страница 1: ...AstroHood S lII RSR AstroHood S lll RSR Ducted HEPA Terminal Hoods INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Страница 2: ...maFrame for Hard Gypsum Ceilings 05 Grille Installation and Removal 07 Filter Unpacking Installation Storage and Operation 07 08 Unpacking 07 Installation 07 Storage 07 Operating Conditions 07 Static...

Страница 3: ...sks including but not limited to electrical and mechanical work equipment handling and safety procedures must be performed in accordance with industry accepted practice and all relevant local state an...

Страница 4: ...e of spun aluminum and the inlet collar is ribbed to secure the flex duct retaining strap A 22 gauge 40 open area removable perforated grille protects the media pack Hanging holes 1 8 in diameter are...

Страница 5: ...ealed to the grid using RTV Dow Corning 732 or GE 102 is recommended 1 Thoroughly clean the mating surfaces of the unit flange and ceiling grid to remove any debris or residue that may inhibit an adeq...

Страница 6: ...osed corners guarantees a smooth cleanable surface White powder coat paint is supplied as standard finish The PermaFrame is ordered separately from the AstroHood unit Drawing Notes Construction 18 ga...

Страница 7: ...ardboard liners Ducted filters will be single or double bagged and packed in reinforced cartons The filter should be handled with extreme care to avoid contact with the media and or face screen While...

Страница 8: ...trolled Temperature Limits Maximum temperatures of 250 F 121 C intermittent and 100 F 38 C steady state Minimum temperature is 32 F 0 C Operating Conditions Temperature The maximum operating temperatu...

Страница 9: ...event heat loss mitigate potential condensation and or provide sound attenuation Determining the use of these options is the responsibility of the design engineer The 2 foil backed option is an alumin...

Страница 10: ...emoval and re installation of such product s or goods including but not limited to labor service costs and shipping charges The same obligations and conditions shall extend to replacement parts furnis...

Страница 11: ...10 APPENDIX B MANUAL REVISION HISTORY Revision Version Revision Date Description of Change Approval...

Страница 12: ...artow FL Columbia MO Fayetteville AR Hudson NY Momence IL Ontario CA Smithfield NC Tijuana Mexico Votorantim Brazil Washington NC Europe Cramlington UK Gasny France Vitoria Spain Ecoparc France Trenci...

Отзывы: