Phenomena
Conditions
Possible reasons
of fault
Actions
Inverter
does not
work
The inverter does
not work after
pressing “RUN”
key, and the
operating indicator
is distinguished.
Terminal of coast to
stop is valid
Check the terminal of
coast to stop
Terminal of prohibit
running is valid
Check this terminal
Terminal of external
stop is valid
Check this terminal
Fixed length stop
Check the setting of
fixed length or clear the
actual length
The operation
control terminal is
not closed under
3-wire control mode
Reset and close this
terminal
Faulty alarm
Clear the fault
Host virtual terminal
set incorrectly
Cancel this function or
reset P9.15
FWD/REV logic of
input terminal is
incorrectly
Check the set of P9.15
Dispay LU
upon power
on
Thyristor or
contactor is
disconnected and
the inverter load is
too large
As the thyristor
orcontactor is
closed, the bus
voltage will reduce
when the inverter
load is large, so
that “LU” is
displayed instead
of “F.Con”
Operate the inverter
after the thyristor or
contactor are completely
closed