4
IF YOU EXPERIENCE AN OUT-OF-GAS SITUATION, DO NOT TRY
TO RELIGHT APPLIANCES YOURSELF
, ask your LP delivery person
to relight pilots for you. Only trained LP professionals should conduct
the required safety checks in accordance with industry standards.
EXTENDED NON-USE PERIODS
WARNING
HYDROGEN GAS CAN BE PRODUCED IN A HOT WATER
SYSTEM SERVED BY THIS HEATER THAT HAS NOT BEEN USED
FOR A LONG PERIOD OF TIME (GENERALLY TWO WEEKS OR
MORE). HYDROGEN GAS IS EXTREMELY FLAMMABLE.
To
reduce the risk of injury under these conditions, it is recommended
that the hot water faucet be opened for several minutes at the kitchen
sink before using any electrical appliance connected to the hot water
system. If hydrogen is present, there will probably be an unusual
sound such as air escaping through the pipe as the water begins to
flow.
THERE SHOULD BE NO SMOKING OR OPEN FLAME NEAR
THE FAUCET AT THE TIME IT IS OPEN.
INSULATION BLANKETS
Insulation blankets available to the general public for external use
on gas water heaters are not approved for use on your A.O. Smith
water heater. The purpose of an insulation blanket is to reduce
the standby heat loss encountered with storage tank water
heaters. Your A.O. Smith water heater meets or exceeds the
ASHRAE/IES 90.1b-1999 standards with respect to insulation and
standby loss requirement making an insulation blanket unnecessary.
WARNING
Should you choose to apply an insulation blanket to this heater,
you should follow these instructions. Failure to follow these
instructions can result in fire, asphyxiation , serious personal
injury or death.
•
Do not apply insulation to the top of the water heater, as
this will interfere with safe operation of the draft hood.
•
Do not cover the outer door, thermostat or temperature &
pressure relief valve.
•
Do not allow insulation to come within 2" (5cm) of the floor
to prevent blockage of combustion air flow to the burner.
•
Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
•
Do obtain new warning and instruction labels from A.O. Smith
for placement on the blanket directly over the existing labels.
•
Do inspect the insulation blanket frequently to make certain
it does not sag, thereby obstructing combustion air flow.
CIRCULATING PUMP
A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the heater.
Install the system in accordance with the current edition of the
National Electrical Code ANSI/NFPA No. 70 or the Canadian
Electrical Code CSA C22.1.
Only all bronze circulators are used with commercial water heaters.
Although circulators are oiled and operated by the manufacturer
some circulators must be oiled again before operating. Please refer
to manufacturer’s instructions.
INSTALLATION INSTRUCTIONS
REQUIRED ABILITY
INSTALLATION OR SERVICE OF THIS WATER HEATER
REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED
TRADESMAN IN THE FIELD INVOLVED. PLUMBING, AIR SUPPLY,
VENTING AND GAS SUPPLY WORK ARE REQUIRED.
GENERAL
The heater is designed to operate on natural or propane gases.
HOWEVER, MAKE SURE the gas on which the heater will operate
is the same as that specified on the heater model and rating plate.
LOCATING THE HEATER
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack or
chimney as practicable, with adequate air supply and as centralized
with the piping system as possible.
WARNING
THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER
AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY
AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY THE
HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING FIRE
OR EXPLOSION. SOME LOCAL CODES PERMIT OPERATION
OF GAS APPLIANCES IF INSTALLED 18" (46CM) OR MORE
ABOVE THE FLOOR. THIS MAY REDUCE THE RISK IF LOCATION
IN SUCH AN AREA CANNOT BE AVOIDED.
DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A
CARPETED FLOOR. A FIRE HAZARD MAY RESULT.
Instead the
water heater must be placed on a metal or wood panel extending
beyond the full width and depth by at least 3" (76.2mm) in any
direction. If the heater is installed in a carpeted alcove or closet, the
entire floor shall be covered by the panel. Also, see the drain
requirements.
THIS HEATER SHALL BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.
WARNING
FLAMMABLE ITEMS
,
PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN
CONTAINERS OF FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.
THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT
WILL BE SUBJECT TO FREEZING.
THE HEATER SHOULD BE LOCATED IN AN AREA WHERE
LEAKAGE FROM THE HEATER OR CONNECTIONS WILL NOT
RESULT IN DAMAGE TO THE ADJACENT AREA OR TO LOWER
FLOORS OF THE STRUCTURE.
WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
DRAIN PAN SHOULD BE INSTALLED UNDER THE HEATER.
Such pans should be fabricated with sides at least 2" (5cm) deep,
with length and width at least 2" (5cm) greater than the diameter of
the heater and must be piped to an adequate drain. The pan must
not restrict combustion air flow.