E01 (blocking error)
The temperature
protection at the top of
the tank has been
activated.
The temperature of the
water at the top of the
tank is > 85
o
C.
None. This is a temporary message that may appear from time to
time, but will disappear automatically.
E03 (lock-out error)
Error in temperature
sensor T
1
at the top of
the tank.
The two temperature
sensors in the tank
detect a differential of >
10
o
C over a period of
at least 60 seconds.
1. Check sensor position and wiring.
2. If necessary, reset the electronic controller. Replace the sensor
if the error persists.
To replace the necessary parts, you must contact your installation
engineer
E04 (lock-out error)
Error in dummy
sensor
(2)
.
The two dummy
sensors in the tank
detect a differential of >
10
o
C over a period of
at least 60 seconds.
1. Check leads from dummy 1 and dummy 2.
2. If necessary, reset the electronic controller. Replace the dummy
sensor if the error persists.
To replace the necessary parts, you must contact your installation
engineer
(1) Temperature sensor T
1
is a '2 in 1' sensor: T
1
, contains 2 NTCs for maximum thermostat and safety thermostat protection.
(2) The flue gas sensor comprises flue gas sensor 1 and flue gas sensor 2.
Symptom
Cause
Solution
Remark
Содержание ADMR-40
Страница 4: ...4 Instruction manual ADMR gis...
Страница 8: ...Table of contents 8 Instruction manual ADMR...
Страница 12: ...Introduction 12 Instruction manual ADMR 1 gis...
Страница 38: ...Installation 38 Instruction manual ADMR 3 is...
Страница 56: ...Shutting down 56 Instruction manual ADMR 10 gis...
Страница 64: ...Main menu 64 Instruction manual ADMR 11 gis...
Страница 78: ...is Instruction manual ADMR 78...
Страница 80: ...Maintenance frequency 80 Instruction manual ADMR 14 is...
Страница 86: ...Performing maintenance 86 Instruction manual ADMR 15 s...
Страница 94: ...Appendices 94 Instruction manual ADMR 17 is...
Страница 96: ...Instruction manual ADMR 96...