NOTE: This drawing is not intended to describe a complete system and is not a replacement for a pro-
fessional engineering drawing. It is intended only as a guide and does not imply compliance with local
building code requirements. Confer with local building officials before installation
.
The Contractor or
engineer is to determine the necessary components and configuration of the particular system to be in-
stalled. It is the responsibility of the engineer or contractor to ensure that the installation is in accordance
with all local building codes.
29
On-Demand
Equipment List
QTY
On-Demand
6
Water Heaters
Domestic Hot Water - Circulation Systems
6 On-Demand Water Heaters with Gas or Electric Tank
Preferred Piping Installation
For this application:
Pump should be controlled by an Aquastat,
Timer or Combination Aquastat and Timer.
Pump to be sized to maintain circulation
loop temperature.
The pump should be sized to overcome the
pressure loss through the tank water heater,
and supply and return plumbing in the
circulation loop. Reference the section
Pump Sizing for Circulation
.
Pump to be of bronze or stainless construc-
tion.
Electronic Connection *
* Refer to On-Demand Accessories
and Model Applicability for
electronic connection details.
Cold Water Supply Line
Gas Supply
On-Demand
Water Heater
Primary
Sub 1
Sub 2
Primary
Sub 1
Sub 2
Hot Water
Supply Line
Smaller Return Line
Can Be Used After
The Last Fixture
Expansion Tank
(Optional) Header Sized One Pipe Size Larger Than Hot
Water Supply Line - (
To eliminate cold water sandwich effect
caused by frequent On/Off operation)
Gas or Electric
Tank Water
Heater
Pressure
Regulator Set to
5 PSI Below
Street Pressure
Building Outlets
Aquastat Connection
Tank Water
Heater sized
to maintain
circulation loop
temperature
On-Demand
Water Heater
On-Demand
Water Heater
On-Demand
Water Heater
On-Demand
Water Heater
On-Demand
Water Heater
Key
Pressure Relief Valve
Check Valve
3/4" Union
3/4" Ball Valve
Boiler Drain Valve
Solenoid Valve
S
Pressure Regulator
Circulating Pump
Mixing Valve