A.O. Smith 101 Series Скачать руководство пользователя страница 39

39

board and is not covered under the limited warranty.

connecting an external supervisory control

The enable/disable circuit is accessed from the CCB’s J6 plug 

inside the CCB enclosure, see Figure 3 on page 8 to locate the 

CCB enclosure. From the factory there is a short (black) jumper 

wire installed between pins 8 and 11 of the J6 plug, see Figure 

61 on page 63 to locate the J6 plug.
install field wiring to the enable/disable circuit:

1. 

Turn  off  power  at  the  water  heater’s  on/off  switch  and  the 

breaker that supplies power to the appliance.

2. 

Locate the CCB enclosure.

3. 

remove  the  screws  from  the  CCB  enclosure  cover  and 

carefully open the CCB enclosure. Note how strain relief for 

the wiring is provided between the cover and enclosure along 

one edge.

4. 

Activate the enable/disable circuit; locate the S1 dipswitch on 

the CCB, see Figure 61 on page 63. 

•  Toggle S1 dipswitch #2 to the open position.
•  Toggle S1 dipswitch #3 to the open position.

5. 

Locate the black jumper wire between pin 8 and 11 on the 

CCB J6 plug, see Figure 61 on page 63 and Figure 62 on page 

64.

6. 

Cut the black jumper wire in the middle.

7. 

Strip approximately 1/2 inch of insulation from the two ends 

of the black jumper wire.

8. 

Using wire nuts connect two field supplied control wires to 

the two ends of the black jumper wire. Wrap electrical tape 

around the wire nut connections.

9. 

Thread the control wires out of the CCB enclosure with the 

other wiring and carefully replace the CCB enclosure cover. 

Ensure all wiring is routed through the indented area provided 

for strain relief. Ensure no wiring is being pinched.

10. 

reinstall the CCB enclosure cover screws and tighten.

11. 

route the control wires inside the junction box on the top of 

the water heater, see Figure 3 on page 8 to locate the junction 

box. Use an available knock-out to route the wires inside the 

junction box.

12. 

install field supplied control wiring and conduit as required 

by  national  and  local  codes  between  the  water  heater’s 

junction box and the external supervisory control. Connect 

the wiring from the external control to the control wires inside 

the junction box using wire nuts and electrical tape.

13. 

Connect  the  control  wiring  to  a  set  of  dry  contacts  on  the 

external control. Follow the control manufacturers instructions 

for making connections.

14. 

restore power to the water heater.

note:

  Whenever  the  external  control  opens  the  set  of  dry 

contacts  used,  heating  operation  will  be  disabled.  Whenever 

the external control closes the set of dry contacts used, heating 

operation  will  be  enabled.  A  diagonal  line  and  circle  appears 

over the thermometer icon on the control system’s display when 

heating operation is disabled. See the Status icons descriptions 

in Table 11 on page 43.

note:

  Ensure  the  water  heater  is  protected  from  freezing 

temperatures  when  heating  operation  is  disabled.  Damage  to 

the water heater caused by freezing temperatures is not covered 

under the limited warranty.

electrical wiring

All  electrical  work  must  be  installed  in  accordance  with  the 

National  Electrical  Code,  ANSi/NFPA  70  or  the  Canadian 

Electrical Code, CSA C22.1 and local requirements.
When installed, the water heater must be electrically grounded 

in accordance with local codes or, in the absence of local codes, 

with the National Electrical Code, ANSi/NFPA 70 or the Canadian 

Electrical Code, CSA C22.1.
if any of the original wire as supplied with the water heater must 

be replaced, it must be replaced with 105°C rated wiring or its 

equivalent, except in the burner housing. in this case use 200°C 

rated wire must be used.

power supply connections

read the requirements for the Power Supply on page 13 before 

connecting power.

correct polarity:

The  water  heater’s  control  system  is  polarity  sensitive  and 

will lock out and disable heating operation if the polarity of the 

power  supply  is  reversed.  The  control  system  will  display  the 

“AC  reversed”  Fault  message  on  the  LCD. The  120  VAC  hot 

wire from the power supply must connect to the black wire in the 

junction box and the 120 VAC neutral wire must connect to the 

white wire in the junction box for correct polarity.
Power supply connections must be made as follows: 

1. 

Ensure  the  power  supply  is  turned  off  at  the  breaker  or 

disconnect switch.

2. 

remove the junction box cover. See Figure 3 on page 8 for 

junction box location. 

3. 

Connect the 120 VAC hot wire from the power supply to the 

black wire in the junction box on top of the water heater with a 

properly sized wire nut. Wrap electrical tape around the wire 

nut and wire end. See wiring diagrams Figure 62 on page 64 

and Figure 63 on page 65.

4. 

Connect the 120 VAC neutral wire from the power supply to 

the white wire in the junction box. Wrap electrical tape around 

the wire nut and wire end. See wiring diagrams Figure 62 on 

page 64 and Figure 63 on page 65.

5. 

Connect  the  ground  wire  from  the  power  supply  to  the 

grounding lug inside the junction box. See wiring diagrams 

Figure 62 on page 64 and Figure 63 on page 65.

6. 

replace  the  junction  box  cover  when  connections  are 

complete.

note:

 Do not apply power to the water heater before installation 

is complete and the water heater is filled with water.

enaBle/disaBle circuit

The  water  heaters  covered  in  this  manual  are  equipped  with 

an  enable/disable  circuit  for  use  with  field  supplied  external 

supervisory  controls  such  as  time  clocks  or  building  Building 

management Systems. The enable/disable circuit may be used 

to disable heating operation during periods when the building is 

unoccupied or there is no demand for hot water.
To  use  the  enable/disable  circuit  it  must  first  be  activated  by 

configuring the S1 dipswitch on the water heater’s CCB (central 

control board), see Figure 61 on page 63. Field supplied wiring 

is then installed between the water heater’s CCB and a set of 

“dry contacts” (no voltage or load) on the field supplied external 

control. 

note:

 The water heater’s enable/disable circuit is a switching 

circuit only: Do not apply external voltage or connect any load 

(iE: relay coil) to this circuit. This will damage the CCB circuit 

Содержание 101 Series

Страница 1: ...NTENANCE LIMITED WARRANTY 500 Tennessee Waltz Parkway Ashland City TN 37015 ANSI NSF 5 ASME CRN WARNING If the information in these instructions is not followed exactly a fire or explosion may result...

Страница 2: ...ng Diagrams 66 Water Piping Diagrams 67 Limited Warranty 74 Table Of Contents Safe Installation Use and Service 3 General Safety Information 4 Precautions 4 Introduction 6 Qualifications 6 iCOMM BACne...

Страница 3: ...ifornia to cause cancer birth defects or other reproductive harm and requires businesses to warn of potential exposure to such substances This product contains a chemical known to the State of Califor...

Страница 4: ...as air escaping through the pipe as the water begins to flow There should be no smoking or open flame near the faucet at the time it is open General Safety Information Read and understand this instru...

Страница 5: ...ment trap in accordance with NFPA 54 Use joint compound or Teflon tape compatible with propane gas Fire and Explosion Hazard Turn off gas lines during installation Contact a qualified installer or ser...

Страница 6: ...Detailed installation diagrams are also found in this manual These diagrams will serve to provide the installer with a reference It is essential that all venting water piping gas piping and wiring be...

Страница 7: ...ENSOR MAIN BURNER radial design BLOWER FLANGE INTAKE AIR combustion air CONNECTION 4 INCH PVC Figure 2 Hot Surface Igniter The control system energizes the Hot Surface Igniter with 120 VAC during the...

Страница 8: ...2 14 15 17 1 18 16 10 8 FRONT Top View Components 1 Water Heater s 120 VAC on off switch 2 Powered anode rods The water heater s covered in this manual are equipped with two powered non sacrificial a...

Страница 9: ...e 16 and Condensate Drain Installation on page 36 Side Views 1 Cleanout access panel covers water heater cleanout opening 2 CCB enclosure see Figure 3 on page 8 for description 3 120 VAC junction box...

Страница 10: ...33 C 39 C 44 C 50 C 56 C 61 C 67 C 72 C 78 C BTH 300 Natural 300 000 88 GPH 1746 1164 873 699 582 499 436 388 349 318 291 269 250 Propane LPH 6610 4406 3304 2644 2203 1888 1652 1469 1322 1201 1102 101...

Страница 11: ...page 21 Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sources if you smell gas Do not store or use gasoline or other flammable v...

Страница 12: ...ulation Pump Wiring Diagrams on page 66 for electrical hookup information Install in accordance with the current edition of the National Electrical Code NFPA 70 or the Canadian Electrical Code CSA C22...

Страница 13: ...upply gas pressure readings are taken while gas is not flowing static pressure AND while gas is flowing dynamic pressure Supply pressure must never fall below the minimum values Supply gas pressures s...

Страница 14: ...rns instantly resulting in severe injury or death Children the elderly and the physically or mentally disabled are at highest risk for scald injury Feel water before bathing or showering Temperature l...

Страница 15: ...er heater is provided with a properly rated sized and certified combination Temperature Pressure Relief Valve T P valve by the manufacturer The valve is certified by a nationally recognized testing la...

Страница 16: ...on See Condensate Drain Installation on page 36 Combustible Material Storage Fire or Explosion Hazard Read instruction manual before installing using or servicing water heater Avoid all ignition sourc...

Страница 17: ...rea through a design of louver or grille or screen is known it shall be used in calculating the size of opening required to provide the free area specified Where the louver and grille design and free...

Страница 18: ...egate input rating of all appliances installed in the enclosure When ducts are used they shall be of the same cross sectional area as the free area of the openings to which they connect The minimum di...

Страница 19: ...section of the manual are a reference for the openings that provide fresh air into confined spaces only Do not refer to these illustrations for the purpose of vent installation See Venting Installati...

Страница 20: ...inal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size gas vent directly below Keep clear of all obstructio...

Страница 21: ...tion the pipe may be stressed or high thermal stresses may be formed when the pipe heats up and expands Install accordingly to minimize such stresses 19 Carefully read the Venting Requirements on page...

Страница 22: ...on the back cover of this manual to order 4 Concentric Termination Part 9006328005 6 Concentric Termination Part 9006144005 Venting Requirements Approved Materials Approved vent and intake air pipe ma...

Страница 23: ...mponents 10 All vent exhaust pipes must be pitched a minimum of a 1 4 inch per foot back to the water heater to allow drainage of condensate 11 If installing 4 inch vent pipe connect the vent pipe to...

Страница 24: ...e intake air and the vent terminations must be a minimum of 24 inches 60 cm above any parapet vertical wall or structure within 10 feet 3 m horizontally See Figure 20 on page 25 4 If installing only v...

Страница 25: ...n page 25 The intake air and vent terminations must have a minimum separation of 24 61 cm measured on center line as shown in Figure 21 on page 25 In colder climates this separation should be increase...

Страница 26: ...eter hole for 6 inch pipe where the pipe s will pass through the wall Note Beware of concealed wiring and piping when cutting through the wall 8 Cut a length s of pipe being installed 3 5 inches 8 9 c...

Страница 27: ...structure as shown in Figure 24 and Figure 25 Note If this required distance to a parapet vertical wall or structure cannot be maintained standard terminations must be used See Vertical Termination In...

Страница 28: ...assembly and secure it to the roof 5 Seal around the plumbing boot or roof flashing 6 Cement the vent cap onto the vent pipe Alternately a field supplied stainless steel screw may be used to secure th...

Страница 29: ...IED LENGTH 25 3 8 INCHES 64 cm MAXIMUM ALLOWABLE LENGTH 45 3 8 INCHES 115 cm MINIMUM ALLOWABLE LENGTH 12 INCHES 30 cm VENT CAP STAINLESS STEEL VENT TERMINAL WITH SCREEN INTAKE AIR PIPE INTAKE AIR CONN...

Страница 30: ...tions are maintained Ensure multiple terminations are arranged or grouped as required Note These clearances must be maintained to prevent the recirculation of vent exhaust gases to the intake air Clea...

Страница 31: ...ALL ROOF Figure 39 Multiple Concentric Termination Arrangements The illustrations on this page show some of the installation arrangements for multiple concentric terminations that are allowed See Mult...

Страница 32: ...32 Venting Arrangements Power Vent Vertical Figure 40 Direct Vent Vertical Figure 42 Power Vent Horizontal Figure 41 Direct Vent Horizontal Figure 43...

Страница 33: ...g Arrangements Direct Vent Vertical Vent Horizontal Intake Figure 44 Direct Vent Vertical Concentric Figure 46 Direct Vent Horizontal Vent Vertical Intake Figure 45 Direct Vent Horizontal Concentric F...

Страница 34: ...to building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30kW 36 i...

Страница 35: ...into building or combustion air inlet to any other appliance 6 inches 15 cm for appliances up to 10 000 Btu hr 3 kW 12 inches 30 cm for appliances between 10 000 Btu hr 3 kW and 100 000 Btu hr 30 kW...

Страница 36: ...PVC cement and PVC primer 1 2 inch PVC pipe minimum length to equal the distance between the water heater and a suitable building drain 1 2 inch PVC fittings elbows and couplings necessary to install...

Страница 37: ...SHUTOFF VALVE TEE FITTING PIPE CAP SEDIMENT TRAP DIRT LEG Figure 52 Ensure all gas pipe is clean on the inside before installation To trap any dirt or foreign material in the gas supply line a sedime...

Страница 38: ...o much torque when connecting the supply gas line to the water heater 7 Install a sediment trap dirt leg as shown in Figure 52 on page 37 8 Install a Main Gas Shutoff valve in the supply gas line as s...

Страница 39: ...limited warranty Electrical Wiring All electrical work must be installed in accordance with the National Electrical Code ANSI NFPA 70 or the Canadian Electrical Code CSA C22 1 and local requirements...

Страница 40: ...ixing Valves on page 14 2 Dishwashing Machines on page 14 3 Temperature Pressure Relief Valve on page 15 4 Closed Systems and Thermal Expansion on page 14 5 For multiple water heater installations see...

Страница 41: ...erature Probe two red wires see Figure 3 on page 8 for location The ECO switch contacts will open when the water temperature reaches approximately 202 F 94 C and close at approximately 140 F 49 C If t...

Страница 42: ...ntrol system The Combustion Blower igniter 24 VAC Gas Valve and anode rods are all powered by the control system The main components of the control system are a UIM user interface module and a CCB cen...

Страница 43: ...See Figure 3 on page 8 for Blower Prover Switch location The Hot Surface Igniter is being energized See Figure 2 on page 7 for Hot Surface Igniter location The igniter has been energized and the cont...

Страница 44: ...from the combustion chamber at the end of a heating cycle Fault The control system has detected a Fault condition Heating operation is disabled until the Fault condition is corrected Power to the wat...

Страница 45: ...ll control system menus from the Main Menu With Temperatures menu selected highlighted in black in the Main Menu screen press the Operational Button under SELECT to enter the Temperatures menu If the...

Страница 46: ...obe Offset 0 F CHANGE BACK HELP Temperatures Bottom of Menu Differential 8 F Tank Temperature 120 F Upper Temperature 122 F Lower Temperature 118 F Heater Regulated to Tank Upper Probe Offset 0 F Lowe...

Страница 47: ...ulated time the control system water heater has been energized Burner On Time Total accumulated time the control system has been in the heating operating state burner run time Cycle Count Total accumu...

Страница 48: ...event will replace the oldest Press the Operational Button under VIEW to view details for each Fault or Alert message stored 1 Blocked Air Intake A7 51 mins ago 2 Blocked Exhaust A8 54 mins ago 3 Low...

Страница 49: ...is menu item Show Contact Information Yes Change Contact Name Change Contact Phone Current Contact Info 000 000 0000 Access Code UPDATE CANCEL Service Contact Information Using the UP and DOWN buttons...

Страница 50: ...on page 38 and repair any leaks found Initial Start Up Required Test Equipment Two U tube manometers recommended ranges 0 14 W C 0 3 5 kPa and 0 35 W C 0 8 7 kPa or pressure gauges Two digital manome...

Страница 51: ...nifold gas pressure to stabilize for several minutes before making further adjustments 4 Replace the gas pressure regulator cover screw 5 Cycle the burner on and off several times to check operation 6...

Страница 52: ...et Point to the lowest temperature setting see Operating Set Point And Differential Adjustment on page 45 2 When the water heater has completed its shut down sequence and enters the standby mode turn...

Страница 53: ...lt in fire or explosion Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control syste...

Страница 54: ...state of other system devices If the tank temperature drops below the Operating Set Point minus the Differential setting the control will automatically return to Step 2 and repeat the operating cycle...

Страница 55: ...period 24 VAC Gas Valve is energized gas flows to Main Burner Is flame sensed at the Main Burner control system monitors the flame sensor Control System Locks Out Displays Fault Msg NO Control System...

Страница 56: ...disable circuit disabling heating operation See Enable Disable Circuit on page 39 The heating capacity of the water heater has been exceeded the water heater is unable to meet demand Operational Probl...

Страница 57: ...gthening the time required to heat water to desired temperature Hot water piping leaks open faucets water heater drain valve leaking or open Sediment or lime scale accumulation may be affecting water...

Страница 58: ...ssure is below the required minimum pressure see Table 4 on page 13 Supply gas is turned off at the Main Shutoff Valve Supply gas pressure is dropping when other gas fired appliances on a common suppl...

Страница 59: ...e 8 for switch location Excessive equivalent pipe length exceeded the maximum number of 90 elbows or wrong pipe size used in the intake air piping system see Venting Requirements on page 22 Balance pl...

Страница 60: ...let the water run until the water is no longer hot Then close the hot water faucet 4 Connect a hose to the drain valve and terminate it to an adequate drain Maintenance General Keep appliance area cle...

Страница 61: ...water heater drain valve to flush the storage tank 7 Flush the water heater storage tank to remove sediment and allow the water to flow until it runs clean 8 Close the water heater drain valve when fl...

Страница 62: ...pped with a powered anode system The anode rods 2 are of a permanent design and do not need replacing unless damaged Inspection and cleaning should be performed once a year Note Follow the instruction...

Страница 63: ...numbers 1 4 On the other side of the dipswitch is the word OPEN The dipswitches are rocker type switches if one side of the rocker is down the other side will be up Pressing a rocker down on the side...

Страница 64: ...VE B CENTRAL CONTROL BOARD C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER INSIDE CCB ENCLOSURE 50VA GROUND STRIP BURNER GROUND BURNER BOLT ON OFF SWITCH GROUND 120 VAC NEUTRAL 120...

Страница 65: ...WER PROVER 24 VAC GAS VALVE B C C 6 J 5 J 4 J 7 J 5 1 J 6 1 J 0 1 J 3 1 J 2 J 3 J 1 J TRANSFORMER 50VA GROUND STRIP BURNER GROUND BURNER BOLT LOW GAS PRESSURE SWITCH 1 BLACK RED 2 WHITE 1 BLACK 2 BLAC...

Страница 66: ...IRCUIT DO NOT SHARE POWER WITH APPLIANCE AS THIS MAY CAUSE ELECTRICAL LINE NOISE AND LEAD TO ERRATIC CONTROL SYSTEM OPERATION CIRCULATING PUMP WIRING DIAGRAM DISHWASHER LOOP WITH TOGGLE SWITCH FIELD S...

Страница 67: ...eview the following 1 See Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 ONE WATER HEATER SINGLE TEMPERATURE WITH BUILDING RECIRCULAT...

Страница 68: ...es on page 14 3 See Temperature Pressure Relief Valve on page 15 ONE WATER HEATER TWO TEMPERATURE WITH HIGH TEMPERAURE LOOP RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF...

Страница 69: ...alve on page 15 ONE WATER HEATER SINGLE TEMPERATURE WITH VERTICAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATI...

Страница 70: ...ONE WATER HEATER SINGLE TEMPERATURE WITH HORIZONTAL STORAGE TANK FORCED RECIRCULATION WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RELIEF VALVE PRESSURE RELIEF VALVE CIRCULATING PUMP DRAIN...

Страница 71: ...llowing 1 See Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 TWO WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND...

Страница 72: ...Mixing Valves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 THREE WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE...

Страница 73: ...ves on page 14 2 See Dishwashing Machines on page 14 3 See Temperature Pressure Relief Valve on page 15 FOUR WATER HEATERS SINGLE TEMPERATURE WITH BUILDING RECIRCULATION LEGEND TEMPERATURE PRESSURE RE...

Страница 74: ...stalled at the heater s and operational at all times The temperature and pressure relief valve installed on the heater is not an acceptable method 4 SERVICE AND REPAIR EXPENSES Under the limited warra...

Страница 75: ...75...

Страница 76: ...500 Tennessee Waltz Parkway Ashland City TN 37015 Technical Support 800 527 1953 Parts 800 433 2545 Fax 800 644 9306 www hotwater com...

Отзывы: