Rack Mounting Jugglers
Rack Mounting Jugglers
Juggler units must be installed in a rack with load-bearing support along the sides, under the rear, or
on a shelf. The rear and side exhaust vents must be kept clear. The front panel should be secured
using an M6 rack mount bolt in each of the top and bottom mounting holes on each side of the unit’s
front panel. These ears alone will not support the weight of the unit.
Mount Jugglers with a minimum one-third rack-unit spacing:
Ø
Juggler Physical Specifications
for dimensions.
Airflow and cooling
Airflow intake is through the filtered vents in the front panel, and exhaust is out through the rear panel
and the rear right-hand side. These vents must all have a clearance of at least 50 mm.