background image

 

Kit 

Cable Size Range  

Cable Insulation  

Lug Cover* 

Maximum 

  Number 

AWG/kcmil (mm

2

O.D. Range 

 I.D. 

Bolt Length

 

 

Feeder 

Motor Lead 

in. (mm) 

in. (mm) 

in. (mm)

 

5302 

2 - 1/0 

4 - 1/0 

0.34 - 0.54 

0.95 

3/4 

 

 

(35 -60) 

(25 - 50) 

(9 - 14) 

(24) 

(19)

 

5303 

1/0 - 250 

2 - 250 

0.40 - 0.80 

1.20 

1-1/4 

 

 

(70 - 120) 

(35 - 120) 

(10 - 20) 

(30) 

(32)

 

5304 

250 - 500 

4/0 - 500 

0.67 - 1.05 

1.70 

1-1/2 

 

 

(150 - 240) 

(120 - 240) 

(17 - 27) 

(43) 

(38)

Motor Lead Pigtail Splice

for 1000 volts (or less) cables with  

one-hole lugs

For two-hole lug connections, use 3M

 Motor Lead Pigtail Splice Kits 

5316 thru 5319 

Instructions

Kit Contents (kit contains 3 splices):

3  Lug Covers

3  Locking Pins

3  Tubes Silicone Grease

3  Mastic Sealing Strips

Kit Selection Table

Table 1

*  Lug cover I.D. - use when calculating kit sizing for a connection of more than two conductors (e.g. 3-way, 4-way, etc. Use of one-hole stacking 

lugs is recommended.)

3M

 

Motor Lead 

Pigtail Splice Kits

for 1000 Volts (or less)

5302, 5303, 5304

78-8126-5500-5-C

Technical Information:

For use on Non-Shielded Cables 1000 Volts  

(or less) with one-hole lugs.

Cable Size Range:
Feeder:  2 AWG-500 kcmil

Motor Lead:  4 AWG-500 kcmil
Copper Conductors

 

Caution

Working around energized systems may cause serious 

injury or death. Installation should be performed by 

personnel familiar with good safety practice in handling 

electrical equipment. De-energize and ground all 

electrical systems before installing product.

CSA Certified for 

600V or Less

Содержание 5300 Series

Страница 1: ...ilicone Grease 3 Mastic Sealing Strips Kit Selection Table Table 1 Lug cover I D use when calculating kit sizing for a connection of more than two conductors e g 3 way 4 way etc Use of one hole stacking lugs is recommended 3M Motor Lead Pigtail Splice Kits for 1000 Volts or less 5302 5303 5304 78 8126 5500 5 C Technical Information For use on Non Shielded Cables 1000 Volts or less with one hole lu...

Страница 2: ...pplicable for approximately 6 152 mm 3 Bolt lugs together See Table 1 for maximum bolt length and Figure 1 for proper bolt lug arrangement C Installation Note If moisture resistance is not required proceed to Step 4 1 To gauge mastic build up in next step temporarily install lug cover over bolted lugs leaving 1 2 13 mm of lug exposed Note Position lug cover so punched holes are positioned between ...

Страница 3: ... A 4 1 R C 4 A 1 T R C 4 U 1 e u l B 1 y e r G 1 l a s r e v i n U 2 4 1 6 1 5 8 3 2 2 0 0 3 3 2 0 0 3 4 2 0 0 3 2 2 6 1 W 1 G W A 2 1 R C 2 A 2 T R C 2 U 1 y e r G 1 n w o r B 1 3 3 2 l a s r e v i n U 1 6 1 5 8 3 7 2 0 0 3 8 2 0 0 3 1 G W A 1 1 R C 1 A 2 T R C 1 U 1 n e e r G 1 n e e r G 1 7 3 2 l a s r e v i n U 0 1 8 3 1 3 0 0 3 2 3 0 0 3 2 3 6 1 W 1 0 1 1 R 5 2 A 1 T R 5 2 U 2 k n i P 2 k n i...

Страница 4: ...s products are based on information believed to be reliable but the accuracy or complete ness is not guaranteed Before using this product you must evaluate it and determine if it is suitable for your intended application You assume all risks and liability associated with such use Any statements related to the product which are not contained in 3M s current publications or any contrary statements c...

Отзывы: