Rack Mounting
23
Rack Mounting
The Advanced RPS is 2U high and can be mounted in a 19-in.
equipment rack. The rack must be well ventilated — 3Com
recommend using an open frame type.
3Com recommend that runners or a tray be fitted in the rack to
support the weight of the Advanced RPS chassis when installed into
the rack.
Using the Rack Mounting Kit
The Advanced RPS is supplied with two mounting brackets and eight
screws. These may be used to secure the unit to the rack when using
runners or a tray. When mounting the unit, you should take note of
the guidelines given below.
CAUTION:
Disconnect all cables from the Advanced RPS before
continuing. Remove the self-adhesive pads from underside of unit, if
already fitted.
Figure 11
Fitting a bracket for rack mounting
1
Place the unit the right way up on a hard, flat surface.
2
Locate a mounting bracket over the mounting holes on one side of
the unit, as shown in Figure 11.
3
Insert the four screws and fully tighten with a suitable screwdriver.
4
Repeat steps 2 and 3 for the other side of the unit.
5
Insert the unit into the 19-in. rack on pre-installed runners, tray, or
other support, and secure with suitable screws (not provided).