background image

QR RECESSED FLUSH 

DRY SPRINKLER 

VK482 (K5.6)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Page 1 of 7

Form No. F_081512     19.06.24      Rev.19.1

1.  DESCRIPTION

The Viking Quick Response Recessed Flush Dry Sprinkler VK482 is a small 

high-sensitivity fusible element sprinkler designed for installation on concealed pipe 

systems where the appearance of a smooth ceiling is desired. The sprinkler orifice 

design, with a K-Factor of 5.6 (80.6 metric*), allows the sprinkler’s efficient use 

of available water supplies for the hydraulically designed fire-protection system. 
The two-piece design of the sprinkler and escutcheon allows installation and test-

ing of the sprinkler prior to ceiling installation. The escutcheon allows for up to 3/4” 

(19.5 mm) of vertical adjustment and can be removed and re-installed, allowing 

access above removable ceiling panels without shutting down the sprinkler system 

and removing the sprinkler.

2.  LISTINGS AND APPROVALS

UL Listed: 

Category VNIV

Refer to the Approval Chart and Design Criteria on pages 3 and 4 for UL 
Listing requirements that must be followed.

3.  TECHNICAL DATA

Specifications:

Minimum Operating Pressure: 7 psi (0.5 bar)

Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).

Thread size: 1” NPT (25mm)

Nominal K-Factor: 5.6 U.S. (80.6 metric*)

* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

Covered by the following U.S. Patents: 8,636,075 and 10,220,231

Material Standards:

Sprinkler Body: QM Brass 

Deflector Assembly: Bronze UNS-C22000 and Brass UNS-C36000

Pin Assembly: Stainless Steel UNS-S30200 and Brass UNS-C23000

Seat Assembly: Brass UNS-C31400 or UNS-C31600

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with 

PTFE Tape

Fusible Element Assembly: Beryllium Nickel and Eutectic Solder

Element Cover: Copper UNS-C11000

Lever Bar Assembly: Copper Alloy UNS-C72500 and Brass UNS-C36000

Lever Arm: Stainless Steel UNS-S31600

Element Assembly: Copper UNS-C11000 and Nickel Alloy

Barrel: Steel Pipe UNS-G10260, Electrodeposited Epoxy Base Finish

Inlet and Barrel End: QM Brass 

Escutcheon Materials:

Flush Dry Escutcheons: Cold Rolled Steel UNS-G10080

Ordering Information:

 (Also refer to the current Viking price list.)

Order Recessed Flush Dry Sprinkler VK482 by first adding the appropriate suffix for the sprinkler and escutcheon finish, the ap-

propriate suffix for the temperature rating, and then the suffix for the length (“A” dimension) to sprinkler base part number. Order 

in a specific length noted as the “A” dimension (see Figure 2). The “A” dimension is the distance from the face of the fitting (tee) to 

the desired finished surface of the ceiling.

These sprinklers are listed and approved in lengths from 4-1/2” to 48” (114 mm to 1,219 mm). 

Finish Suffix: White Polyester = M-/W

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E

For example, sprinkler VK482 a White Polyester finish and a 165 °F (74 °C) temperature rating, and “A” length of 10” = Part No. 

18385MC/W10.

Viking Technical Data may be found on 

The Viking Corporation’s Web site at 

http://www.vikinggroupinc.com.

The Web site may include a more recent 

edition of this Technical Data Page.

Replaces Form No. F_081512 Rev 15.1.P65 

(Added patent number.)

Содержание VK482

Страница 1: ...llowing U S Patents 8 636 075 and 10 220 231 Material Standards Sprinkler Body QM Brass Deflector Assembly Bronze UNS C22000 and Brass UNS C36000 Pin Assembly Stainless Steel UNS S30200 and Brass UNS C23000 Seat Assembly Brass UNS C31400 or UNS C31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Fusible Element Assembly Beryllium Nickel and Eutectic Solder El...

Страница 2: ...thority Having Jurisdiction Refer to specific installation standards 3 Part number shown is the base part number for the replacement escutcheon For complete part number refer to current Viking price list schedule Figure 1 Sprinkler Installation and Correct Use of Wrench Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench A Dry F...

Страница 3: ...vals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S 5 Painted finish consists of Polyester Baked Enamel Other paint colors are available on request with the same listings as the standard paint colors Listings and approvals apply for any paint manufacturer Contact Viking for additional informati...

Страница 4: ...baffles are installed in accordance with NFPA 13 Locate no less than 4 102 mm from walls Maximum distance from walls shall be no more than one half of the allowable distance between sprinklers The distance shall be measured per pendicular to the wall The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed IMPORTANT Always refer t...

Страница 5: ...9058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 5 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 4 Recessed Flush Dry Sprinkler Seal Figure 3 Recessed Flush Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area ...

Страница 6: ...nical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 6 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 5 Recessed Flush Dry Sprinkler Escutcheon Instructions Push adapter up until stopped Rotate adapter clock wise until stopped Let adapter drop until stopped Rotate outer cup until it comes into contact with the ceiling 1 2 3 4 5 ...

Страница 7: ...n Recess Instructions Figure 7 Recessed Flush Dry Sprinkler Escutcheon Recess Instructions Measure from Escutcheon Adapter Sprinkler Base to the bottom face of Escutcheon Cup for recess measurement Also see figure 2 NOTE Do not measure from Element Assembly NOTE After installed the inner escutcheon adapter must not extend beyond the outer escutcheon cup This will result in exceeding the maximum re...

Страница 8: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 9: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 10: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 11: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 12: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 13: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 14: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 15: ... the sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may af...

Страница 16: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 17: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 18: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 19: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: