background image

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KLIC-SG vT 

 

 

 

 

 

KNX – F3/F4 Gateway 

for Indoor Samsung A/C Units 

 

 

 

 

 

 

 

 

U

S

E

R

 M

A

N

U

A

L

 

 

 

 

ZCLSGVT 

 

 

 

Application program version: [1.1]  

User manual edition: [1.1]_a 

 

 

 

www.zennio.com

  

 

 

Summary of Contents for KLIC-SG vT

Page 1: ...KLIC SG vT KNX F3 F4 Gateway for Indoor Samsung A C Units USER MANUAL ZCLSGVT Application program version 1 1 User manual edition 1 1 _a www zennio com...

Page 2: ...llation 4 1 3 Start Up and Power Loss 5 2 Configuration 6 2 1 General 6 2 2 A C Gateway 9 2 2 1 Configuration 9 2 2 2 Fan 19 2 2 3 Initial Configuration 23 2 2 4 Scenes 25 2 2 5 Error Handling 26 2 3...

Page 3: ...actual status of the unit can be monitored and periodically sent to the KNX bus to inform other devices The most outstanding features of KLIC SG vT are Bidirectional control of indoor Samsung A C unit...

Page 4: ...amming mode making the associated LED 1 light in red Note if this button is held while plugging the device into the KNX bus the device will enter into safe mode The LED will blink in red every 0 5 sec...

Page 5: ...ed in the device packaging and also available at www zennio com 1 3 START UP AND POWER LOSS Depending on the configuration some specific actions will be performed during the device start up The integr...

Page 6: ...unctions A C gateway The latter entails all functions specific to KLIC SG vT i e all the functions related to interfacing with the A C unit and to the management of the climate control system ETS PARA...

Page 7: ...the project Heartbeat Object to Send 1 that will be sent periodically with value 1 to notify that the device is still working still alive Note the first sending after download or bus failure takes pla...

Page 8: ...ion mode either Automatic Heating Cooling Fan or Dry or reading the current mode respectively See section 2 2 1 for further options AC Fan Percentage Control and AC Fan Percentage Control Status allow...

Page 9: ...ced functions Simplified Operation Mode which allows switching between heating and cooling operation modes by means of a 1 bit object Fan which allows advanced configuration of the ventilation see sec...

Page 10: ...le wireless controller Filter which allows to know the filter status of the A C Unit Ionizer which allows to activate the air purification function These functionalities imply changes in the state of...

Page 11: ...cal Support https support zennio com 11 ETS PARAMETRISATION The Configuration window under A C Gateway provides the following parameters Figure 5 A C Gateway Configuration OPERATION MODES Figure 6 A C...

Page 12: ...nit operating modes Additionally a simplified mode can be configured to select Cooling and Heating mode Simplified Mode Only Cooling Heating disabled enabled in addition to the Mode and Mode Status 1...

Page 13: ...ol loop Once enabled a secondary parameter will show Sending Type Variation Periodic Periodic Variation sets whether the above object should be sent only in case of a change in the value periodically...

Page 14: ...alue will be rounded to X 0 if Y 5 or to X 5 if Y 5 Status object will be updated to the last setpoint temperature value received by the A C unit after a complete communication cycle and will be sent...

Page 15: ...Temperature Setpoint Upper Limit 2 Byte object that allows changing the upper limit at run time AC Temperature Setpoint Upper Limit Status 2 Byte object with the upper limit current value Notes If Mi...

Page 16: ...or a similar event trigger Automatic off will be also active if the unit is previously in off state so the unit will not be able of being on until this situation finishes During the temporary switch o...

Page 17: ...l state will be the last one KLIC SG vT is aware of Custom see section 2 2 3 SCENES Figure 13 A C Gateway Configuration Scenes Scenes disabled enabled allows setting up different scenes up to 5 consis...

Page 18: ...operating time retransmission period If set to 0 the periodic send is disabled When operating time object reaches its maximum value 65535h it will be sent through KNX bus in spite of the fact that the...

Page 19: ...the Fan tab KLIC SG vT allows advanced configuration of the fan functionality The following features are displayed 360 CST allows configuration for 360 cassette unit enabling custom objects and config...

Page 20: ...r Flow and AC CST Air Flow Status for airflow control of this IDU type Fan Speeds 3 4 specifies the number of the fan levels distinguished by A C unit KLIC SG vT allows the sending of fan speed orders...

Page 21: ...ntrol 1 bit disabled enabled enables the AC Fan Step Control one bit object If the parameter is enabled the following options are displayed Non Cyclical the automatic mode will be ahead the minimum sp...

Page 22: ...er the polarity can be configured by parameter Fan Stop Object Polarity 0 Fan Stop Protection 1 Normal Operation 0 Normal Operation 1 Fan Stop Protection sets the polarity of the above object Flaps di...

Page 23: ...vated in fan mode when Wind Free mode is activated or when the A C unit is switched off 2 2 3 INITIAL CONFIGURATION The custom initial configuration allows setting the desired status that KLIC SG vT w...

Page 24: ...he value of the setpoint temperature will be kept Only available if the Setpoint parameter remains disabled 16 25 30 C Note this initial setpoint value may be modified by the setpoint limits during ru...

Page 25: ...PARAMETRISATION After enabling this function see section 2 2 1 a new tab named Scenes will be incorporated to the tab tree It allows setting up different scenes up to 5 consisting each of them in a se...

Page 26: ...e Fan tab See section 2 2 2 Air Flow Direction4 No Change Spot Mid Wide Swing Horizontal Flaps No Change Swing Off Swing On Vertical Flaps No Change Swing Off Swing On Setpoint disabled enabled Value...

Page 27: ...METRISATION The error handling function does not entail any parameter configuration The following objects are available by default Internal error objects AC Internal Error Communication 1 Bit object t...

Page 28: ...A C Unit Error Active Error 1 Bit object which indicate that there is an error in the A C unit AC A C Unit Error Error Code 14 Byte object that supplies the error code In case the A C unit reports an...

Page 29: ...etector for the connection of a motion detector from Zennio 2 3 1 BINARY INPUT Please refer to the Binary Inputs user manual available in the KLIC SG vT product section at the Zennio website www zenni...

Page 30: ...xecution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterisable communication objects The result after ex...

Page 31: ...s 16 30 C 6 2 Bytes I C W DPT_Value_Temp 273 00 670433 28 AC Temperature Setpoint Lower Limit 16 30 C 7 2 Bytes O C R T DPT_Value_Temp 273 00 670433 28 AC Temperature Setpoint Lower Limit Status 16 30...

Page 32: ...wing Status 0 Swing Off 1 Swing On 1 Bit O C R T DPT_Switch 0 1 AC Horizontal Flaps Swing Status 0 Swing On 1 Swing Off 24 1 Bit I C W DPT_Switch 0 1 AC Vertical Flaps Swing 0 Swing Off 1 Swing On 1 B...

Page 33: ..._Temp 273 00 670433 28 Ix Current Temperature Temperature Sensor Value 64 68 1 Bit O C R T DPT_Alarm 0 1 Ix Overcooling 0 No Alarm 1 Alarm 65 69 1 Bit O C R T DPT_Alarm 0 1 Ix Overheating 0 No Alarm 1...

Page 34: ...Constant Value Percentage 0 100 2 Bytes C T DPT_Value_2_Ucount 0 65535 Ix Short Press Constant Value Integer 0 65535 2 Bytes C T 9 xxx 671088 64 670433 28 Ix Short Press Constant Value Float Float Val...

Page 35: ...ight On Off Switching 0 1 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Long Press Run Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Long Press Save Scene Sending of 128 191 1 Bit O...

Page 36: ...0 65535 Ix Presence Waiting Time 0 65535 s 94 123 2 Bytes I C W DPT_TimePeriodSec 0 65535 Ix Presence Listening Time 1 65535 s 95 124 1 Bit I C W DPT_Enable 0 1 Ix Presence Enable According to paramet...

Page 37: ...147483648 2147483647 LF 4 Byte Data Entry x 4 Byte Data Entry 215 216 217 218 219 220 221 222 223 224 1 Bit O C R T DPT_Bool 0 1 LF Function x Result 1 Bit Boolean 1 Byte O C R T DPT_Value_1_Ucount 0...

Page 38: ...n and send us your inquiries about Zennio devices https support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio...

Reviews: