background image

always the best climate

Decorative radiators

Comfortable indoor ventilation

Heating and cooling ceilings

Clean air solutions

Installation, Service and User Manual

Zehnder EASY 5.0

Summary of Contents for CALADAIR EASY 5.0

Page 1: ...always the best climate Decorative radiators Comfortable indoor ventilation Heating and cooling ceilings Clean air solutions Installation Service and User Manual Zehnder EASY 5 0...

Page 2: ...iagnosis_________________________________________________________________________ 23 14 1 General_______________________________________________________________________________________________ 23 14 2...

Page 3: ...ction _______________________________________________________________________________________ 62 23 3 Thermal output ___________________________________________________________________________________...

Page 4: ...type of appliance and work Use the necessary Personal Protective Equipment to avoid injury related to electrical mechanical injuries from contact with metal sheets sharp edges etc and acoustic hazards...

Page 5: ...creen is powered by a 230V AC 24V DC transformer and communicates with the CLD 283 controller in Modbus RTU RS485 via the Ext DISP port The screen is the master and the controller is the slave Communi...

Page 6: ...ere is no active communication P2 RxTx Status LED for port 2 reserved for communication with another expansion controller TCP IP Status LED for TCP IP port P B Status LED of the board Printed Board Th...

Page 7: ...s UI AGND Common UI1 UI4 Inputs can be configured as analogue input AI or digital input DI depending on the machine version see electrical diagram for machine 1 TCP IP port Port reserved for communica...

Page 8: ...ISPLAY To extend the supplied electrical harness use a 2x0 75mm cable or equivalent for the 24V DC power supply A Belden 3106A cable or equivalent for communication It is not possible to operate the o...

Page 9: ...ter the heat recovery When it is not operating there is no heat recovery and this is also the case when running in free cooling or free heating mode In the case of a plate heat exchanger the recovery...

Page 10: ...point supply air temperature supply air temperature control mode The measured return air temperature is higher than the setpoint return air temperature return air temperature control mode 5 4 Demand a...

Page 11: ...e function configured to start the unit is active or there is a request for operation from the BMS The start up sequence takes a total of 120 seconds During this time the alarms are disabled except fo...

Page 12: ...he supply air fan is switched off after 180 seconds The return air fan is switched off 30 seconds later The fresh air and return air registers are closed 5 seconds after the return air fan has stopped...

Page 13: ...nit is switched off All of the following conditions must be met to activate the function The user has authorised the cooling operation accessible parameter Fewer than 4 days have passed since the unit...

Page 14: ...ivation conditions are met again the fan offset will only be active after a time limit of 60 minutes from the time the cooling function was exited When cooling is active The DO output cooling NO is cl...

Page 15: ...he fresh air bypass anti icing function must be reset This does not always happen instantly depending on the PID settings The factory setting of the outdoor activation temperature threshold is 100 C w...

Page 16: ...should be done independently if necessary When the anti fire function is activated the bypass control output of the plate heat exchanger is deactivated and the fresh air is diverted from the plate he...

Page 17: ...onding reduced speed pressure volume Normal operation The fan rotates at the corresponding normal speed pressure volume 2 Return air fan setpoint Auto The fan runs at the speed pressure volume request...

Page 18: ...Navigation and menu access 3 Time change setting summer winter automatic XXXV 6 Navigation and menu access 4 Time period settings XXXV 6 Navigation and menu access 5 Fan setpoint configuration XXXV 6...

Page 19: ...end time Principle of timetable setting 00 00 00 00 means that the period is not active 00 00 24 00 means that the period is permanently active 07 00 19 00 means that the period is active from 07 00...

Page 20: ...n is activated the ventilation unit will operate in normal operation Is off no active time schedule and the forced running in reduced or normal operation is activated the unit will operate in reduced...

Page 21: ...ion and the operating costs of the ventilation unit Access path to the function Access level Service Step 1 Step 2 Step 3 Step 4 From screen Area to click Holiday calendar Time settings Holiday calend...

Page 22: ...schedule 00 00 07 00 to avoid disrupting the operation of the night cooling function Below is an example of time schedule left and ventilation right settings for the optimal operation of a LOBBY cont...

Page 23: ...ort and air quality The rest of the time the ventilation unit runs in reduced operation to limit energy consumption If the conditions for activating the night cooling function are met it will operate...

Page 24: ...s P1RxTx and TCP IP on the controller faceplate indicate that there is communication between the controller and an external device BMS CTM Communication takes precedence over external setpoints DI whi...

Page 25: ...ry this will most likely lead to a malfunction or undesired behaviour of the machine Wiring Reverse wiring can lead to incorrect operation For example if a dry contact for external control to force th...

Page 26: ...at is carried out on the machine during operation Unfortunately in some cases it is possible that the fault will not allow some outputs to be checked because the machine is stopped broken down as in t...

Page 27: ...se it allows the operation of certain actuators to be stabilised at specific points thus making it possible to take readings or measurements absorbed current pressure temperature etc or to check the o...

Page 28: ...on unit permission to restart Class A and B are identical It is useful to be able to distinguish between actions for the same type of resetting B C The alarm is automatically acknowledged when the cau...

Page 29: ...cause depends on an analogue value for example temperature too high pressure or volume too low etc 15 6 Alarm state or status When there is an alarm it can take on several states depending on the sta...

Page 30: ...sed for more than just the filters One month corresponds to 30 days and the countdown starts as soon as the unit is switched on When the power is off and the controller is not operating the countdown...

Page 31: ...it 30s The minimum threshold depends on each machine model see table below Faulty fan Faulty fan power supply Speed control signal problem HS controller output faulty wiring connection between fan and...

Page 32: ...structs the air flow in the machine 54 Return filter alarm C 600s See Id 53 Supply and return filter alarm See Id 53 Supply and return filter alarm 56 Frost protection alarm THA C 120s Rapid stop The...

Page 33: ...atic relay can become conductive resulting in a permanent power supply to the electric coil 78 Internal battery error C 120s Normal stop The charge level of the internal battery has reached the minimu...

Page 34: ...l The unit stops when the alarm is triggered To restart the temperature must fall below 55 C and the alarm must be manually acknowledged Supply air fan VAS defective The unit s isolation damper and th...

Page 35: ...ort circuit 166 Return pressure transducer fault A 5s Normal stop Only for LOBBY Faulty missing transducer and or faulty wiring open or short circuit 167 Supply air volume transducer fault A 5s Normal...

Page 36: ...m3 h 1800 m3 h 350 m3 h 540 m3 h CARMA 9035 SILVERTOP 35 1700 m3 h 3000 m3 h 610 m3 h 900 m3 h CARMA 9048 2000 m3 h 3500 m3 h 770 m3 h 1050 m3 h SILVERTOP 52 2750 m3 h 3900 m3 h 740 m3 h 1170 m3 h CA...

Page 37: ...ing sequence 16 BMS communication 16 1 General The controller has the following 2 external communication ports Port P1 Modbus RTU RS485 slave or Bacnet MS TP TCP IP port Modbus TCP or Bacnet IP or web...

Page 38: ...the same communication line the master controller requires a minimum silent interval of 14 characters 16ms at 9600 baud between the last controller response and the first question from the next contro...

Page 39: ...evel Expert Step 1 Step 2 Step 3 Step 4 From screen Area to click Parameter Possible value range Baud rate 9600 14400 19200 28800 38400 57600 76800 115200 Address slave 1 247 Number of data bits 8 Par...

Page 40: ...e not accessible The functions supported by the controller are as follows XXX address of the variable in Modbus protocol Supported functions Type Read and write binary value BV 10XXX Read binary value...

Page 41: ...456789 BBMD X X A Bacnet Broadcast Management Device is used to detect controllers that are attached to different Bacnet IP subnets and separated by an IP router Neither viewable nor configurable from...

Page 42: ...n the tables use the generic Modbus standard There is no address offset to be expected the 1st existing variable is addressed to the value 0 not 1 Scaling factor 10 means that the value read must be d...

Page 43: ...gister 466 short AV 40376 Only for ECO and DIVA versions Supply air fan pressure Pa X 10 Input Register 311 short AV 40311 Only for LOBBY versions Return air fan pressure Pa X 10 Input Register 312 sh...

Page 44: ...supply or return by air law Outdoor temperature 4 air law C X X 10 150 Holding Register 820 short AV 30820 Used only if temperature control supply or return by air law Outdoor temperature 5 air law C...

Page 45: ...Holding Register 847 short AV 30847 Only for ECO and DIVA versions Return air fan normal speed setpoint X X 10 70 Holding Register 851 short AV 30851 Only for ECO and DIVA versions Return air fan red...

Page 46: ...QUATTRO versions factory setting depends on machine model Fan balancing 3 CO2 m3 h X X 0 1 See details Holding Register 1041 short AV 31041 Only for QUATTRO versions factory setting depends on machine...

Page 47: ...nsor fault X Input Status 191 bool BV 20191 0 no alarm 1 alarm present Only for machine equipped with plate heat exchanger Supply pressure transducer fault X Input Status 175 bool BV 20175 0 no alarm...

Page 48: ...retrieved directly from the PG 5 0 touchscreen from the communication menu see XVI 5 IP configuration DHCP 18 Temperature control modes Access path to the function Access level Expert Step 1 Step 2 S...

Page 49: ...ther so that the main cooling system is not overloaded and runs unnecessarily causing needless energy consumption Uses a maximum of free energy free cooling or free heating from the outside air in the...

Page 50: ...24V AC to be relayed used according to the configuration Authorisation to run the heating generator Authorisation to run the circulator or heating pump no degumming cycle On Off output for cooling nee...

Page 51: ...ed for each outdoor temperature point The setpoints are adjusted at the factory for a supply air law To avoid excessive energy consumption while maintaining acceptable comfort it may be possible to ra...

Page 52: ...emperature setpoint variables whether it is using supply air law or return air law Switching from supply air to return air or vice versa therefore requires the setpoint to be adjusted for each outdoor...

Page 53: ...UATTRO versions variable threshold set in the CLD 283 controller in accordance with the AHU model see XV 11 Fan feedback and difference thresholds 19 2 ECO controller The ECO controller is an open loo...

Page 54: ...pm the fan offset is kept constant at 30 which gives a resulting speed of 70 of the maximum speed 40 30 70 An intermediary point set at 900ppm and 15 offset makes it possible to make the behaviour of...

Page 55: ...sted individually and continuously by means of a PID algorithm in order to obtain a measured actual pressure equivalent to the setpoint pressure adjusted in the controller regardless of the variable n...

Page 56: ...operation pressure setpoint in order to potentially manage 2 different pressure levels or to further increase the resulting air volume when night cooling is activated In the latter case it must be en...

Page 57: ...greater precision because the air volume is known and therefore better controlled It does not depend on the state of clogging of the filters and the minimum volume of the unit can be managed more prec...

Page 58: ...r to the battery heating elements The PWM signal period is 60 secs not adjustable The PWM value is directly proportional to the calculated heating requirement The PWM is translated directly to the DO...

Page 59: ...water heating coil The electric heating coil is equipped with an overheating safety thermostat set at 100 C which protects the machine from accidental overheating e g static relay failure The overheat...

Page 60: ...ol signal is zero 0V The hot water feed rate to the hot water heating coil is zero When the hot requirement is at its maximum the control signal is at its maximum 10V and the hot water feed rate to th...

Page 61: ...is used as a position setpoint for controlling the modulating 3 way valve When the cold requirement is zero the control signal is zero 0V The cold water feed rate to the cooling coil is zero When the...

Page 62: ...g coil is to maintain a sufficient temperature factory setting 5 C at the fresh air inlet of the plate heat exchanger in order to avoid any risk of icing of the condensed water vapour on the return ai...

Page 63: ...cooling and anti icing bypass sequences The electric fresh air preheating coil is equipped with an NC normally closed safety thermostat THSD set at 100 C which cuts off the power supply to the KD con...

Page 64: ...el drive motor starts when the signal exceeds 1 1V and stops when the signal drops below 0 6V Above 9 5V the exchanger operates at maximum speed Between 1 1V and 9 5V the rotation speed of the wheel f...

Page 65: ...nger The bypass operates when there is A need to modulate heat recovery which is the case when There is a heating requirement and the return air temperature is higher than the fresh air temperature th...

Page 66: ...nger on the return air side when the outside air temperature is particularly low winter period installation at altitude etc the cold fresh air volume is diverted from the exchanger in order to prevent...

Page 67: ...n function see ANTI ICING FUNCTION BY REDUCING THE SUPPLY AIR VOLUME The anti icing function is activated when the exhaust temperature drops below 3 C and stops when the temperature rises above 4 C Th...

Page 68: ...ctory setting for all machines the controller interprets this as a fan malfunction and may activate certain alarms If an electric heating coil is used it is only activated if the pressure is higher th...

Page 69: ...ory set in the control programme for each machine The supply and return air volume is also used as a fan run feedback signal When the measured volume is below a certain threshold different for each ma...

Page 70: ...open in the idle state when there is no air volume and closes when fan air volume results in a differential pressure of more than 25 Pa Reference point Details 1 Setting jumpers 2 Zero setting sensor...

Page 71: ...inals 1 and 3 is closed 2 Pressure switch electrically disconnected The voltage between terminals 1 and 3 is a 0V DC electrically connected pressure switch The corresponding digital input DI must indi...

Page 72: ...sensor wiring plug as close as possible to the corresponding controller input 32 CO2 sensor The CO2 sensor converts the CO2 concentration in the air stream in which it is installed return into an ana...

Page 73: ...a digital algorithm integrated in the controller that continuously calculates a setpoint e g fan speed setpoint from the difference error between the adjusted setpoint e g supply air pressure and the...

Page 74: ...ific devices Presence of an external disturbance that generates air volume instabilities in the machine e g 90 curved air duct immediately after leaving entering the unit gusts of wind etc External di...

Page 75: ...misleading but quite normal This difference in operation is very important when conducting a diagnosis on DOs or on a consumer connected to them The table below summarises the values to be obtained f...

Page 76: ...tware versions of the display and controller can be accessed on the Programme info page from the symbol on the Menu page Display technology LCD TFT Liquid Cristal Display Thin Film Transistor Touchscr...

Page 77: ...values of the machine To resetting or adjusting the maintenance counter interval To active alarms and the history of recorded alarms Service 3333 All Guest level functions as well as Setting the clock...

Page 78: ...agnosis is required Z MASTER V1122 CSY INM Zehnder Easy5 0 Supply Fan Temperature Return Fan Temperature Fresh air temperature Bypass temperature Preheating temperature Current setpoint Measure Curren...

Page 79: ...le inspection tasks to be spread out and a possible next service date to be planned 35 6 Navigation and menu access The Main Menu page is accessed from the home page 1 button Guest level access User l...

Page 80: ...tment of thermal related setpoints Service Temperature control mode Temperature setpoint s Temperature limits Reading the controller s input output values Service Analogue inputs AI UAI Digital inputs...

Page 81: ...Zehnder EASY 5 0 81 Notes Z MASTER V1122 CSY INM Zehnder Easy5 0...

Page 82: ...Zehnder EASY 5 0 82 Notes Z MASTER V1122 CSY INM Zehnder Easy5 0...

Page 83: ...Zehnder EASY 5 0 83 Notes Z MASTER V1122 CSY INM Zehnder Easy5 0...

Page 84: ...Company 1st line of address Town Country email website Z MASTER V1122 CSY INM Zehnder Easy5 0 en subject to change without notice...

Reviews: