background image

AUTOMATIC PHASE SWITCH FAZ APM-20 

INSTRUCTION MANUAL

ZAMEL 

Sp. z o.o.

ul. Zielona 27, 43-200 Pszczyna, Poland

tel. +48 (32) 210 46 65, fax +48 (32) 210 80 04

www.zamel.com

, e-mail: [email protected]

plik: inst_ext_gb_apm-20 | modyfikacja: 30.12.2016

APPEARANCE

FEATURES

TECHNICAL PARAMETERS

DESCRIPTION

●  maintaining uninterrupted power sup-

ply of  a single-phase receiver, 

●  three-phase  power  supply  L1-L2-L3 

(L1-priority phase),

●  automatic phase switching during po-

wer  supply  failure  or  its  value  decre-

ase below 180 V AC,

●  switching time at a level of 150 ms
●  voltage  switch  threshold,  switching 

time and voltage hysteresis have de-

fault settings and cannot be changed 

by a user,

●  high voltage measuring accuracy – re-

lative error < 1%,

●  voltage  measurement  of  distorted  si-

gnals (True RMS),

●  output  load–  maximum  16 A  for AC1 

loads,

●  signalling the parameters of particular 

voltage supply phases – 3 x LEDs,

●  mounting in distribution boards (TH35 

rail) – width of 2 modules.

The automatic phase switch APM-20 is 

designed to ensure uninterrupted power 

supply of a one-phase receiver in case 

of phase loss or RMS voltage value de-

crease  below  the  norm.  The  main  ad-

vantage of the device is a small relative 

voltage measurement error, which does 

not exceed 1% even for highly distorted 

waves. The  above  is  a  result  of  an  im-

plementation of the True RMS converter. 

The APM-20 device is supplied by three 

phases L1, L2, L3 with the L1 phase as 

the  prior  one.  The  voltage  switch  thre-

shold  (180  V  AC),  switching  time  (150 

ms)  and  voltage  hysteresis  (10  V  AC) 

have default settings and cannot be 

changed by a user. Each phase parame-

ters are optically signalled by means of 

LEDs  on  the  front  panel  of  the  device. 

The internal system of output contacts 

assures an increased resistance to their 

bonding and protects against phase-to-

-phase short circuit. The maximum out-

put capacity should not exceed 16 A for 

AC1 class receivers. APM-20 is mounted 

in distribution boards (TH35 rail). The ca-

sing has the width of 2 modules.

Power supply terminals: L1, L2, L3, N
Nominal supply voltage:  3 x 230 V AC + N

Nominal frequency:  50 Hz

Nominal power consumption:  1,7 W / 3,8 VA – per 3 phases

Priority phase:  L1

Signalling parameters of power supply phases:  3 x red LED (L1, L2, L3)

Output terminals:  L, L, N, N

Nominal output voltage:  230 V AC

Maximum output capacity:  16 A for AC1 class devices 

Switch threshold for L1, L2, L3:  <180 V AC

Voltage hysteresis:  10 V AC

Switching time:  ~150 ms

Względny błąd pomiaru napięcia: <1%

Distorted signal measurement:  yes – True RMS

Number of terminal clamps:  8

Cross-section of connecting cables:  0,2 do 2,5 mm

2

Operating temperature range:  -20 ÷ +45 °C

Operating position:  free

Casing mounting:  TH35 rail (2-MOD casing)

Casing protection degree: IP20

Protection level:   II

Overvoltage category:  II

Pollution degree: 2 

Surge voltage:  1 kV (PN-EN 61000-4-5)

Dimensions:  monomodular 90x35x66 mm

Weight:  0,14 kg

Reference standard:  PN-EN 60669-1, PN-EN 60669-2-1,

PN-EN 61000-4-2,3,4,5,6,11

The symbol means selective 

collecting of electrical and 

electronical equipment. It 

is forbidden to put the used 

equipment together with other 

waste.

Signalling parameters

of power supply phases

Output terminals

(to connect the load)

Power supply terminals

Reviews: