background image

User’s

Manual

1

Thank you for purchasing the JUXTA Signal Conditioner.

Please read through this manual before use for correct handling.

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

Phone: +81-422-52-7179  Facsimile: +81-422-52-6793

http://www.yokogawa.com/ns/juxta/im/

You can download the latest manuals from the following website:

IM 77J01A01-01E

5th Edition June 2018 (YK)

CAUTIONARY NOTES FOR SAFE USE OF THE 

PRODUCT

This User’s Manual should be carefully read before installing and 

operating the product. Please keep this User’s Manual for future 

reference.

For more information of the safety precautions, please refer to the 

“Precautions on the Use of the JUXTA Series (IM 77J01A00-91Z1)”.

The related manuals and general specifications are shown in the 

table below.

Doc. Name

Doc. Number 

Precautions on the Use of the JUXTA Series (User’s Manual) IM 77J01A00-91Z1

Model VJA1 Distributor (User’s Manual)

IM 77J01A01-01E

(This manual)

Model VJA1 Distributor (General Specifications)

GS 77J01A01-01E

User’s manuals in the above table are essential parts of the 

product; keep it in a safe place for future reference.

This manual is intended for the following personnel;   

 •

Engineers responsible for installation, wiring, and maintenance 

of the equipment.

 • Personnel responsible for normal daily operation of the 

equipment.

The following symbol is used on the product and in this manual to 

ensure safe usage.

 WARNING

Calls attention to actions or conditions that could 

cause serious or fatal injury to the user, and indicates 

precautions that should be taken to prevent such 

occurrences.

 CAUTION

Calls attention to actions or conditions that could 

cause injury to the user or damage to the instrument 

or property and indicates precautions that should be 

taken to prevent such occurrences.

CHECKING PRODUCT SPECIFICATIONS 

AND PACKAGE

(1) Checking the Model and Product Specifications

  Check that the model and specifications indicated on the 

nameplate attached to the main unit are as ordered.

(2) Packaged Items

  Check that the package contains the following items:

 •

VJA1: 1 unit

 

Standard Accessories: 

 •

Tag number label: 1 sheet

 •

User’s manual (IM 77J01A01-01E, this manual): 1 copy

 •

User’s manual (IM 77J01A00-91Z1): 1 copy

GENERAL

The VJA1 is a compact, plug-in type distributor that is used 

in combination with a two-wire type transmitter to convert the 

transmitter’s 4 to 20 mA DC signals into isolated DC current or 

DC voltage signals.

•  HART communication: VJA1/H (option code /H)

  Bi-directional relay of HART communication signals is possible 

while the field devices and the higher-level device are isolated 

from each other.

MODEL AND SUFFIX CODES

Model

Suffix codes

Description

VJA1

-0

x x

-A

x x

0

/x

Distributor

Fixed code

-0

Always -0

Output

1

1 output

2

2 outputs

Power supply

6

100-240 V AC/DC

*1

7

15-30 V DC

*2

Input signal

-A

4 to 20 mA DC

Transmitter power supply: 

25.25±0.25 V DC

Output-1 signal

A

4 to 20 mA DC

B

2 to 10 mA DC

C

1 to 5 mA DC

D

0 to 20 mA DC

E

0 to 16 mA DC

F

0 to 10 mA DC

G

0 to 1 mA DC

1

0 to 10 mV DC

2

0 to 100 mV DC

3

0 to 1 V DC

4

0 to 10 V DC

5

0 to 5 V DC

6

1 to 5 V DC

7

−10 to +10 V DC

Z

Custom order 

*3

Output-2 signal

A

4 to 20 mA DC

6

1 to 5 V DC

N

No output-2

Z

Custom order 

*3

Fixed code

0

Always 0

Option

/SN

No socket (with socket if not 

specified)

/C0

Coating 

*4

/FB

Fuse bypass 

*4

/H

With HART communication 

*5

*1: Operating range: 85 to 264V

*2: Operating range: 12 to 36V

*3: DC voltage signal or DC current signal

*4: When option code /C0 or /FB is specified, the conformity to the safety 

and EMC standards is excluded. CE marking is not applicable.

*5: When option code /H is specified, the output-1 signal code is “A” (4 to 

20 mA DC) only.

Model VJA1

Distributor

(Isolated Single-output and

Isolated Dual-output Types)

Reviews: